User levels, Point display, Eagle quantum premier devices – Det-Tronics S3 Graphics User Manual

Page 133

Advertising
background image

12-18

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

EAGLE QUANTUM PREMIER DEVICES

User Levels

The “User Level Editor...”

provides a means for limiting

access to the “Acknowledge”,

“Remove”, “Manual Oi”, “Inhibit”,

“IR Calibration”, “Manual Oi

(FIRE)” and “Reset” buttons

for the module which are accessible from the devices point display. The default

value is “0” and provides access to all users.

Change these values to match a user account configuration and security needs.

Point Display

The MIR X3301 has a custom “Point Display”

that can be accessed from either the Point

Display button on the Command Bar or from

the Online Mode.

The point display provides a single window

view of all available real-time data for the

device.

Alarm Logs
The top right quadrant of the display shows

the last eight alarms with their date and time

data.

Analog Input Track

The top left quadrant shows a dynamic 60 second history of the measured variable (IR counts) for the detector.

The input track scrolls from left to right with the most current data at the “pen” on the left margin. The display

updates once every five seconds.

Manual Oi Log
The bottom left quadrant of the point display shows the detectors manual Optical Integrity (Oi) log. The last eight

manual tests are shown with the date, time and a PASS/FAIL indicator.

Status & Diagnostics
The middle portion of the point display shows the discrete status and health indicators for the detector.

Buttons
There are six buttons that can send commands to the detector including; remove, inhibit, reset, Manual Oi,

Manual Oi (FIRE) and IR Calibration.

MIR X3301 • USER LEVELS