13-52

EQP LOGIC EDITOR

Version 6.0

EQP LOGIC EDITOR

The final step in completing the example network is to

link the NOT gates output variable to an appropriate

point. Double clicking on the “Output Variable” opens

the “Output Selection...” dialog box.

This dialog box presents the database in the same

manner as described on the previous page for the

input selection process.

For this example, the LON data structure has been

expanded, a Signal Audible Module (SAM) with the

tagname “SAM-014” has been expanded and the

Binary data point “Activate Continuous” for the Lamp

output has been selected. Selecting the “OK” button

will close the “Output Selection...” dialog box and link

this output to the output variable as shown below.

The network is now complete, when the High Gas Alarm for ECL-016 goes “ON” the lamp controlled by SAM-014

goes “OFF”.

Using the “Comment Tool” a description can be added to explain the purpose of the output.

LOGIC CREATION • VARIABLE LINKING