Chapter 3 Operation
POWER CON
PCON-CA/CFA
112
Judging completion of pressing operation
The operation monitors the torque (current limit value) in percent in “Pressing” of the position
table and turns pressing complete signal PEND ON when the load current satisfies the
condition shown below during pressing. PEND is turned ON at satisfaction of the condition if
the work is not stopped.
(Accumulated time in which current reaches pressing value [%])
– (accumulated time in which current is less than pressing value [%])
255 ms (Parameter No.6)
Current
Time
Pressing [%]
Operation
start
Approach end
Pressing start
200ms
20ms
75ms
295ms
200ms + 75ms – 20ms 255ms
Pressing complete (PENDoutput)
Contactiong wark
Decrease in current due
to movement of work