[Startup Adjustment with Teaching Tool when Control Circuit Incomplete]

Situation

Possible cause

Check/Treatment

Operation is not

performed even though

the teaching tool is

connected, and power to

the controller motor and

control circuit is

supplied.

(the emergency stop

switch is released on the

teaching tool)

Cable treatment or mode selection.

1) Emergency stop condition

2) Servo OFF condition

3) In pause

1) Supply 24V DC to EMG-

terminal of the power connector.

Warning

If the process of 1) is conducted,

put back the setting as soon as

the adjustment work is finished.

Starting the operation without

putting it back may cause a

serious accident since the

emergency stop is set invalid.

2) 3) Put the operation mode switch

on the front panel of the

controller to “MANU” side, and

select the teach mode on the

teaching tool.