Chapter 9

Appendix

POWER CON

PCON-CA/CFA

234

3) Dummy plug (Accessories)

Connect a dummy plug to the teaching pendant connecting connector.

Make sure to connect a dummy plug if the AUTO mode is specified.

Without the connection, it will be the emergency stop condition.

Model : DP-4

Plug : TX20A-26PH1-D2P1-D1E (JAE)

Signal

Short-circuit processing.

9.3

When Connecting Power Supply with + Grounding

When using PCON-CA with + grounding, there is a risk of short-circuit of 24V DC power supply

if connected to the PC. This is because many PCs have the communication ground (GND) and

the frame ground (FG) connected inside and short-circuit occurs through the frame ground.

Also, if controllers with different 24V DC power supplies are connected with serial

communication, the communication line may become the route of controller power supply in

some cases depending on the timing to turn on the power, resulting in the malfunction of the

communication line.

Troubleshooting is summarized separately in [ME0271 Caution for + Grounding 24V Power

Controller]. Please refer to it.