Chapter 8

Troubleshooting

POWER CON

PCON-CA/CFA

211

Alarm

Code Alarm Level

Alarm Name

Cause/Treatment

0C0

Actual speed excessive

Cause

: This indicates the number of motor rotation

exceeded the number of allowable rotation.

1) The slide resistance of the actuator is locally

high.

2) The load is increased too much due to a

external force.

With the reasons above, it can be considered a

sudden speed increase has occurred before

detecting the servo error.

Treatment : Even though this would not occur in normal

operation, check if there is any abnormality in the

parts assembly condition. Also check if there is a

possibility that an external force may be applied

in the direction of the actuator movement.

0C1

Operation

release

Servo error

Cause

: It indicates 2 seconds has passed without

making a move since a move command was

received.

1) Connection error or wire breakage of

motor/encoder cables.

2) Brake is not released (when equipped with a

brake).

3) Load to the motor is high due to external

force.

4) The resistance in the actuator sliding

operation is large.

Treatment : 1) Check for the motor/encoder cable wiring

condition.

2) Supply 24V DC 150mA to the BKRLS terminal

on the power supply connector and if you can

see an improvement, it is considered the

controller failure. Please contact IAI.

3) Confirm that there is no error in the

mechanical part assembly condition.

4) If the loaded weight is within the allowable

range, turn the power OFF and check the

resistance in sliding operation by moving the

slider with hand.

0C8

Overcurrent

Cause

: The output current in the power circuit section is

increased abnormally.

Treatment : This alarm will not be generated in normal

operation. It can be considered as the insulation

degradation of the motor winding or malfunction

of the controller. Please contact IAI.

0C9

Cold start

Overvoltage

Cause

: The voltage of the power regenerative circuit has

risen above the threshold.

Treatment : A malfunction of a component inside the

controller can be considered. Please contact IAI.