Chapter 9

Appendix

POWER CON

PCON-CA/CFA

218

9.1.2 Detailed Connection Diagram of Communication Lines

SIO Converter

4-way Junction (Manufactured by AMP : 5-1473574-4)

(SGA) A

(SGB) B

0V

1
2

3

1
2

7

1
2

7

1
2

3

1
2

3

4

1
2

3

4

1
2

3

4

Personal

Computer

Touch Panel Teaching

J4, J5

Mini DIN

8 pin

Double Shield Cable

(Note 1)

Recommended : Taiyo Cabletec Corp.

HK-SB/20276XL

(AWG22)

e-CON Connector

(Manufactured by AMP : 4-1473562-4)

Cover Color : GN

Controller

Link Cable

CB-RCB-CTL002

PCON 2nd Unit

SIO Connector

SIO Connector

Class D grounding

PCON 1st Unit

e-CON Connector

(Manufactured by AMP :

4-1473562-4)

Housing Color : GN

e-CON Connector

(Manufactured by AMP : 3-1473562-4)

Cover Color : OR

Controller

Link Cable

CB-RCB-CTL002

YW

OR

BL

YW

OR

BL

SGA
SGB

GND

SGA

SGB

GND

(A)

(B)

SGA
SGB

0V

Shield

(Note 1) Apply a 2-pair shielded cable.

When connecting a cable other than recommended to (A) and (B), make sure to use a

hard-cored cable equivalent to the vinyl cable (KIV) dedicated for control devices with

the sheath outer diameter from 1.35 to 1.60mm. Using cables with outer diameter out

of the specification may cause poor contact to occur.

Caution: When cables with outer diameter out of the specification are used, use a

terminal block instead of 4-direction junction. In this configuration, disconnect

the e-CON connector of the link cable. If an error possibly caused by poor

contact occurs frequently, replace the junction with the terminal block.

9.1.3 Axis No. Setting

Set an axis number by using the axis number setting switch on the front panel of PCON.

Possible axis numbers range from 0 to F by 16 axes.

After the setting, turn off the power of PCON and then on it again.

Caution: The axis number must be unique.

Adjust the arrow to a

desired position using a

flathead screwdriver.