Chapter 8

Troubleshooting

POWER CON

PCON-CA/CFA

214

Alarm

Code Alarm Level

Alarm Name

Cause/Treatment

0E0

Overload

Cause

: 1) The work weight exceeds the rated weight, or

an external force is applied and the load

increased.

2) If the actuator is equipped with a brake, the

brake is not released.

3) The slide resistance of the actuator is locally

high.

Treatment : 1) Check the work and its surrounding area to

remove the cause.

2) Supply 24V DC 150mA to the BKRLS terminal

on the power supply connector and if you can

see the condition is cancelled, it is considered

the controller failure. Please contact IAI. If the

brake is not released, the brake itself may be

faulty, cable may be disconnected, or the

controller may be faulty. Please contact IAI.

3) In the case that the work can be moved by

hand, move it. Then, check that there is no

location where a sliding resistant is too large.

Check if the installation face is distorted.

When the error occurs in operation of the

actuator only, Please contact IAI.

Caution

Restart the operation after making sure to remove the

cause.

If you cannot determine that the cause is removed

completely, wait for at least 30 minutes before turning on the

power to prevent the motor coil from burning.

0E5

Cold start

Encoder receipt error

Cause

: This shows the data was not received in normal

condition from the encoder side to the controller

(applicable part to Simple Absolute).

1) Cable breakage of encoder cable or

connector connection failure

(If the detail code in the error list of the

teaching tool is 0002H.)

2) Effect of noise

(If the detail code in the error list of the

teaching tool is 0001H.)

3) Malfunction of component (communication

part) inside the actuator

4) A faulty part inside the controller

(communication part).

Treatment : 1) Check if any wire breakage on a connector

and the condition of wire connections.

2) Interrupt the power to the peripheral

equipment and activate only the actuator. If

any error does not occur, it might be caused

by noise. Take proper measures against

noise.

If the cause is due to (3) or (4), it is necessary to

replace the actuator (motor part) or controller.

If the cause cannot be specified, please contact

IAI.