Chapter 1 Specifications Check

POWER CON

PCON-CA/CFA

34

1.7 Noise Elimination and Mounting Method

(1) Noise Elimination Grounding (Frame Ground)














(2) Precautions regarding wiring method

1) Wire is to be twisted for the power supply.

2) Separate the signal and encoder lines from the power supply and power lines.

(3) Noise Sources and Elimination

Carry out noise elimination measures for

electrical devices on the same power path

and in the same equipment. The following

are examples of measures to eliminate noise

sources.

1) AC solenoid valves, magnet switches and relays

[Measure] Install a Surge absorber parallel with the

coil.

2) DC solenoid valves, magnet switches and relays

[Measure] Mount the windings and diodes in parallel.

Select a diode built-in type for the DC relay.

Do not share the ground wire with or

connect to other equipment. Ground

each controller.

Earth Terminal

Class D grounding

(Formerly Class-III grounding :

Grounding resistance at 100:or less)

Copper Wire :

Connect to an ground cable with

diameter 1.6mm (2mm

2

) or more.

Connect the ground line

together to the main unit

using the fixing screw.

Controller

Other

equipment

Controller

Other

equipment

Other

equipment

Surge absorber

Relay

coil

Relay coil

R

C

+24V

0V

+24V

0V

+

-

Connect the ground cable using

the tapped hole for FG connection

on the main unit.

M3 x 5 nickeled pan head

machine screw

(enclosure dedicated for

DIN rail fixed type)

Screw fixed type

DIN rail fixed type