Chapter 1 Specifications Check

POWER CON

PCON-CA/CFA

32

1.4.2 Pulse Train Input Output Interface

Line Driver Input

Specification

Sends input pulse from the host unit that is installed with a line

driver 26C31 or equivalent

Host Unit

Positioning Unit

PCON

PP
/PP

NP
/NP

Pulse Train

Form

Including active high and active low

1.5

Options

1.5.1 Pulse converter : AK-04

The pulse converter converts command pulses in the open collector mode to those in the

differential mode.

Use this converter if the host controller sends output pulses in the open collector mode.

Item

Specification

Input Power

Supply

24V DC r10% (MAX. 50mA)

Input Pulse

O/C (Collector current MAX. 12mA)

Input Frequency 200kpps or less

Output Pulse

Differential output equivalent to 26C31 (MAX. 10mA)

Mass

10g or less (excluding cable connector)

Accessories

37104-3122-000FL (e-CON Connector) 2 Units

Cover Color : YW

Applicable wire AWGNo.24 to 26 (Less than 0.14 to 0.3mm

2

,

finished O.D. I1.0 to 1.2mm)

 

Caution

1) Use the pulse converter in the surrounding temperature range between 0qC and

40qC.

2) The temperature increase of about 30qC occurs during operation. Accordingly,

neither install several pulse converters in close contact nor install them within a

duct. Do not install the pulse converter near other heating devices.

3) If more than one pulse converter are installed, set a pulse converter apart from

another by 10mm or more.