Chapter 2 Wiring

POWER CON

PCON-CA/CFA

42

Category

Signal

Abbreviation

Signal Name

Function Description

Relevant

Sections

PEND/INP Position complete

Turns ON in the positioning band range after actuator operation.

The INP signal will turn OFF if the position deviation exceeds the

in-position range. PEND and INP can be switched over by the

parameter.

3.2.3

3.2.4

3.2.5

PM1 to

PM256

Completion Position No. The position No. reached after the positioning completion, is

output (binary output).

3.2.3

3.2.4

HEND

Home return completion This signal will turn ON when home return has been completed.

It will be kept ON unless the home position is lost.

3.2.3

3.2.6

ZONE1

ZONE2 Zone

Turns ON if the current actuator position is within the range set to

the parameter.

3.2.3

PZONE Position zone

This signal will turn ON when the current actuator position enters

the range specified the position data after position movement.

Even though it can be used together with ZONE1, PZONE will

become only available for operation by the set position number.

3.2.3

RMDS

Operation Mode Status

Output

Outputs the operation mode status. It turns on when the controller

is on Manual Mode.

3.2.3

*ALM

Alarm

Turns ON when the controller is in normal condition, and turns

OFF when an alarm is generated.

3.2.3

ALM1 to

ALM8

Alarm Code

The detail of the alarm is output with binary code when an alarm

more than the operation cancel level is issued.

3.2.3

MOVE

Moving

Turns ON during the actuator is moving (including home-return

operation and pressing operation).

3.2.3

3.2.4

SV

Servo ON

This signal will remain ON while the servo is ON.

3.2.3

*EMGS Emergency Stop Output

This signal remains ON while the controller is under the

emergency stop reset condition and turns OFF when the

emergency stop condition is enabled. (Regardless of alarms.)

3.2.3

MODES Teaching Mode Output

This signal will turn ON while the teaching mode is enabled by

the input of the mode signal and will turn OFF when the mode

changes to the normal mode.

3.2.4

WEND

Writing Complete

It is OFF during the teaching mode and turns ON when the

writing by PWRT Signal is complete. It turns OFF when PWRT

Signal turns OFF.

3.2.4

PE0 to PE6 Current Position

Number

In the solenoid valve mode, this signal will turn ON when the

actuator completes moving to the target position.

3.2.5

LS0 to LS2 Limit Switch Output

Turns ON when the current actuator position is within the range

of positioning band (r) of the target position. It is output even

before the movement command and the servo is OFF if the

home-return operation is completed.

3.2.6

*ALML

Light Error Output

Outputs when a message level alarm is generated.

(It is necessary to set parameter)

8.4

LOAD

(Note 1)

Load output judgment

signal

Output is made when the current exceeded the value set in

“Threshold” for certain time

(Note)

within the range of “Zone+” and

“Zone-“ in the position data during the pressing operation.

Note It is to be utilized to judge if the press-fitting set in

Parameter No.50 has executed in the normally condition.

3.2.4

3.2.5

Output

TRQS

(Note 1)

Torque level output

Turns ON when the motor current has exceeded the value set in

“Threshold” in the position data in such cases as the slider (or

rod) hitting an obstacle while in pressing operation, and turns

OFF when current goes below the value.

3.2.4

3.2.5

Signal with “*” expresses the signal of active low. It is ON when the power is applied to the controller, and turns OFF when the

signal is output.

(Note 1) It is the signal dedicated for High-Thrust Actuator (CFA type). Use this as a reference output for other actuators.