Chapter 8

Troubleshooting

POWER CON

PCON-CA/CFA

199

Situation

Possible cause

Check/Treatment

ALM in the status display

LEDs turns on when the

power is supplied.

(1) Occurrence of alarm

(2) During emergency-stop.

1) Was the emergency-stop switch.

2) EMG- on the power supply

connector is not connected.

(1) Check the error code with the

teaching tool being connected

and remove the cause by

referring the alarm list.

[Refer to 8.4 Alarm List.]

(2) 1) Release the emergency stop

switch.

2) Check the connection of the

power connector (EMG-).

[Refer to 2.3.1 Wiring Layout

of Power Supply Connector.]

The host controller

(PLC) cannot control

PIO (24V DC I/O).

PIO signal communication is disabled.

1) 24V DC power for PIO is not

supplied.

2) Poor contact of flat cable

3) The operation mode setting switch

on the front panel is on “MANU”

side.

4) The +/- pins of 24V DC power for

PIO are connected inversely.

1) Check the PIO power voltage. If

a single power supply is

connected with large load, the

power supply voltage may drop

or the output may be shut down

depending on power units.

2) Are the PIO cable connectors

inserted to the mating

connectors securely? Check the

input signals on the I/O monitor

of the teaching tool such as PC

software.

Caution

In I/O cable conduction check,

do not widen female pins of the

connectors. Failure to follow this

may cause poor contact.

3) Can such operation as jogging

be performed from the teaching

tool such as PC software? Set

the operation mode setting

switch on the front panel and

restart the controller.

[Refer to Name for Each Parts

and Their Functions.]

4) Reverse connection of the PIO

power supply does not affect the

input circuit but makes the

output circuit faulty. Check if the

I/O of the host controller (PLC)

operates normally.