Pcon-ca/cfa, Power con – IAI America PCON-CA User Manual

Page 223

Advertising
background image

Chapter 8

Troubleshooting

POWER CON

PCON-CA/CFA

215

Alarm

Code Alarm Level

Alarm Name

Cause/Treatment

0E8

Cold start

A- and B-phase wire

breaking

Cause

: Encoder signals cannot be detected correctly.

1) The motor/encoder relay cable or supplied

actuator cable is disconnected or its

connector is not plugged in correctly.

2) The encoder itself is faulty.

Treatment : 1) Check if any wire breakage on a connector

and the condition of wire connections.

If the cables are normal, faulty encoder is

suspected. Please contact IAI.

0ED

Absolute encoder error

detection 1

Cause

: The current position has changed while the

controller is reading or saving the absolute data.

Treatment : Avoid a condition that gives vibration to the

actuator.

0EE

Absolute encoder error

detection 2

Cause

: The position data cannot be detected properly in

the Simple Absolute applicable type encoder.

1) When the power is supplied for the first time

to Simple Absolute applicable type (before

executing absolute reset)

2) Voltage drop of absolute battery.

(If the detail code in the error list of the

teaching tool is 0001H.)

3) Wire breakage or connector contact failure of

motor/encoder relay cable or actuator

enclosed cables, or attempted to insert and

remove the cables

(If the detail code in the error list of the

teaching tool is 0002H.)

4) Changed the parameters of controller

Treatment : 2) Supply the power for 72 hours or more and

after charging the battery enough, perform the

absolute reset operation.

If the same failure occurs often even with

enough battery charge, it is considered the

end of the battery life. Replace the battery.

Conduct an absolute reset for 1), 2) and 4).

[Refer to Chapter 6 Absolute Reset and Absolute

Battery]

0EF

Absolute encoder error

detection 3

The encoder for the Simple Absolute applicable type cannot

detect the position information properly. (Encoder overspeed

error)

Cause

: The current position changed with a speed more

than the rotation velocity setting by an external

cause during the power shutoff.

Treatment : Set the rotation velocity to a higher speed than

what currently is. If the same failure occurs

again, it is necessary to have an absolute reset.

[Refer to Chapter 6 Absolute Reset and Absolute

Battery]

0F1

Operation

release

Field bus link error

Cause

: Error detected in field network link

Treatment : Reboot the power. Please contact us if the

problem is not solved with this action.

0F2

Field bus module error

Cause

: Error detected in field network circuit board

Treatment : Check the parameter settings.

0F3

Field bus module not

detected

Cause

: Field network circuit board could not be

detected.

Treatment : Reboot the power. Please contact us if the

problem is not solved with this action.

0F4

Cold start

Mismatched PCB

The PCB is not applicable for the connected motor in the

startup check.

Cause

: The actuator may not match the controller.

Check the model.

Treatment : Should this error occur, please contact IAI.