Pcon-ca/cfa, Power con, Chapter 7 i/o parameter – IAI America PCON-CA User Manual

Page 174: I/o parameter list (continued)

Advertising
background image

Chapter 7 I/O Parameter

POWER CON

PCON-CA/CFA

166

I/O Parameter List (Continued)

No.

C

at

eg

or

y

Name

Symbol

Unit

(Note1)

Input Range

Default factory

setting

for

Positioner

Mode

for Pulse

Train

Mode

Relevant

sections

60

B Deviation counter clear input

FPIO

0: Enabling

1: Disabling

0

{

3.3.5 [5]

61

B Torque limit command input

FPIO

0: Enabling

1: Disabling

0

{

3.3.5 [6]

62

B Pulse count direction

FPIO

0: Forward motor rotation

1: Reverse motor rotation

In accordance with

actuator

(Note2)

{

3.3.5 [7]

63

B Command pulse input mode

(Pulse train mode)

CPMD

0 to 2

1 (pulse-train and

moving direction

angle)

{

3.3.4 [2]

64

B Command pulse input mode

polarity

CPMD

0: Positive Logic

1: Negative Logic

0

{

3.3.4 [2]

65

B Electronic gear numerator

CNUM

1 to 4096

2048

{

3.3.4 [1]

66

B Electronic gear denominator

CDEN

1 to 4096

125

{

3.3.4 [1]

67

B Compulsory stop input

FPIO

0: Enabling

1: Disabling

0

{

3.3.5 [8]

71

B Feed forward gain

PLFG

0 to 100

0

{

{

7.2 [56]

77

D Ball screw lead length

LEAD

mm

(deg)

0.01 to 999.99

In accordance with

actuator

(Note2)

{

{

7.2 [57]

78

D Axis operation type

ATYP

0: Linear Axis

1: Rotary Axis

In accordance with

actuator

(Note2)

{

7.2 [58]

79

B Rotary axis mode selection

ATYP

0: Normal Mode

1: Index Mode

In accordance with

actuator

(Note2)

{

7.2 [59]

80

B Rotational axis shortcut selection

ATYP

0: Disabling

1: Enabling

In accordance with

actuator

(Note2)

{

7.2 [60]

83

B Absolute unit

ETYP

0: Incremental

1: Simple Absolute Type

In accordance with

specification at order

accepted

{

7.2 [61]

84

A Fieldbus operation mode

(Note4)

FMOD

0 to 4

Separate volume

{

Separate

volume

85

A Fieldbus node address

(Note4)

NADR

0 to 127

Separate volume

{

Separate

volume

86

A Fieldbus baud rate

(Note4)

FBRS

0 to 4

Separate volume

{

Separate

volume

87

E Network type

(Note4)

NTYP

0 to 7

Separate volume

{

Separate

volume

88

D Software limit margin

SLMA

mm

0 to 9999.99

In accordance with

actuator

(Note2)

{

{

7.2 [66]

90

C Fieldbus I/O format

(Note4)

FPIO

0 to 3

Separate volume

{

Separate

volume

91

C Current limit value at stopping due

to miss-pressing

FSTP

0: Current limit value

during movement

1: Current limit value

during pressing

0

{

7.2 [68]

110

B Stop method at servo OFF

FSTP

0: Rapid stop

1: Deceleration to stop

0

{

7.2 [69]

111

B Calendar function

FRTC

0: Does not use the

calendar timer

1: Use the calendar

timer

1

{

{

7.2 [70]

112

B Monitoring mode

FMNT

0: Does not use

1: Monitor function 1

2: Monitor function 2

0

{

{

7.2 [71]

113

B Monitoring period

FMNT

msec

1 to 100

1

{

{

7.2 [72]

Note 1 The unit (deg) is for rotary actuator and lever type gripper. It is displayed in mm in the teaching tools.

Note 2 The setting values vary in accordance with the specification of the actuator. At shipment, the

parameters are set in accordance with the specification.

Note 4 These parameters are exclusively used for the field network type.