Chapter 8

Troubleshooting

POWER CON

PCON-CA/CFA

209

Alarm

Code Alarm Level

Alarm Name

Cause/Treatment

0A1

Cold start

Parameter data error

Cause

: The data input range in the parameter area is not

appropriate.

Example 1) This error occurs when the

magnitude relationship is apparently

inappropriate such as when 300mm

was incorrectly input as the value of

the soft limit negative side while the

value of the soft limit positive side

was 200.3mm.

Example 2) In rotary axis, when the index mode

is changed to the normal mode and

the soft limit negative side is 0, this

error is issued. Set the soft limit

negative side to a value -0.3mm is

added to the outer side of the

effective stroke. [Refer to 7.2 [2] Soft

limit +, Soft limit -]

Treatment : Change the value to the appropriate one.

0A2

Position data error

Cause

: 1) A move command was input when no target

position was set in the “Position” field of a

position No. in the position table.

2) The value of the target value in the “Position”

field exceeded the Parameter No.3 and 4

“Soft limit set value”.

3) A target position was specified in the

“Position” field by relative coordinate in the

solenoid valve mode 2 of PIO pattern 5.

Treatment : 1) Set the target position.

2) Change the target position value to the one

within the soft limit set value.

3) The target position cannot be set by relative

coordinate (incremental feed).

0A3

Position command data

error

Cause

: 1) The speed or acceleration/deceleration value

during direct numeric specification exceeded

the maximum set value.

Treatment : 1) Edit point table to input a proper value.

0A4

Command counter

overflow

Cause

: The number of input command pulses exceeded

the range of -134217728 to +134217728

(H'F8000000 to '07FFFFFF).

Treatment : Attempt to make the value of the electrical gear

ratio smaller (make the movement against the

unit bigger).

0A7

Operation

release

Command deceleration

error

Cause

: Because there is not enough deceleration

distance when the deceleration is changed to a

lower setting during the operation, the actuator

exceeded the soft limit when deceleration was

made from the current position with the

deceleration after the change.

Soft limit

Deceleration starting position

not resulting in soft limit overshoot

If a command is issued here,

soft limit overshoot will occur.

The cause is that the timing to make the next

movement command when the speed was

changed during the operation was late.

Treatment : Make the timing earlier for the movement

command for the deceleration speed change.