Chapter 8

Troubleshooting

POWER CON

PCON-CA/CFA

212

Alarm

Code Alarm Level

Alarm Name

Cause/Treatment

0CA

Overheat

Cause

: This indicates overheat (90qC or more) of the

components inside the controller.

1) Operation is performed with the load condition

exceeding the specified range.

2) High temperature around the controller.

3) Load to the motor is high due to external

force.

4) A faulty part inside the controller.

Treatment : 1) Revise the operation condition such as

decreasing the acceleration/deceleration

speed.

2) Lower the ambient temperature of the

controller.

3) Confirm that there is no error in the

mechanical part assembly condition.

(Note) This error would not normally occur. If it occurs,

confirm there is not (1) to (3) above. If the same error

is issued again even after confirming (1) to (3) is not in

the condition, it is considered to be a malfunction.

Contact IAI.

0CC

Cold start

Control power source

voltage error

Cause

: The control power voltage dropped less than the

voltage drop threshold (120% of 24V DC =

28.8V).

1) The voltage of 24V DC power supply is high.

2) A faulty part inside the controller.

3) During acceleration/deceleration and

servo-on that use the remote sensing function

of 24V DC power supply, the current

consumption rises transiently.

Using the remote sensing function with a

power supply with no enough current capacity

may cause overvoltage responding to the

current change.

Treatment : 1) 2) Check the voltage of the power supply.

3) Think to use a power supply with enough

current capacity or not to use the remote

sensing function.

In the case that the voltage is normal, please

contact IAI.

0CE

Operation

release

Drop in control supply

voltage

Cause

: The control power voltage dropped less than the

voltage drop threshold (80% of 24V DC = 19.2V).

1) The voltage of 24V DC power supply is low.

2) A faulty part inside the controller.

Treatment : Check the voltage of the power supply.

In the case that the voltage is normal, please

contact IAI.

0D4

Cold start

Drive Source Error

Cause

: 1) Motor power input voltage (input to MPI

terminal) is too large

During acceleration/deceleration and

servo-on, the current consumption rises

transiently. Using the remote sensing function

with a power supply with no enough current

capacity may cause overvoltage responding

to the current change.

2) Overcurrent is generated on the motor power

supply line.

Treatment : 1) Check the power voltage input to MPI

terminal. Think to use a power supply with

enough current capacity or not to use the

remote sensing function.

2) Check the wire layout between the actuator

and controller.