Pcon-ca/cfa, Power con – IAI America PCON-CA User Manual

Page 208

Advertising
background image

Chapter 8

Troubleshooting

POWER CON

PCON-CA/CFA

200

[In the case of Positioner Mode]

Situation

Possible cause

Check/Treatment

Both position No. and

start signal are input to

the controller, but the

actuator does not move.

There is a problem either in PIO signal

treatment, position table setting or

operation mode selection.

1) Servo OFF condition

2) The pause signal is OFF.

3) Positioning command is issued to a

stop position.

4) There is no positioning data set to

the commanded position number.

1) Is the status display LED SV

turned ON? [Refer to Name for

Each Parts and Their Functions]

Turn ON the servo-on signal

SON of PIO.

2) Operation is available when PIO

pause signal *STP is ON and

pause when it is OFF. Turn it

ON. [Refer to 2.1.2.]

3) Check the sequence or the

settings of the position table.

4) It will generate Alarm Code 0A2

“Position Data Error”. Conduct

the position table setting.

(Note) Refer to 2.1.3 [3] PIO Circuit for PIO signal.

[In the case of Pulse Train Control Mode]

Situation

Possible cause

Check/Treatment

In spite of inputting

pulse-train to the

controller, the actuator

does not move.

PIO signal processing or parameter

setting is incorrect.

1) Servo OFF state

2) The pause signal is OFF.

3) The pulse-train type, a parameter, is

selected incorrectly.

4) The positive/negative logic of

pulse-train, a parameter, is selected

inversely.

5) The unit moving distance per pulse,

which is a setting condition of

electronic gear ratio, a parameter, is

too small.

1) Is the status display LED SV

turned ON? [Refer to Name for

Each Parts and Their Functions]

Turn ON the servo-on signal

SON of PIO.

2) Operation is available when PIO

pause signal *STP is ON and

pause when it is OFF. Turn it

ON. [Refer to 2.1.2.]

3) Check the pulse train type.

[Refer to 3.3.4 [2] Format

Settings of Command Pulse

Train.]

4) Check the positive/negative

logic of pulse-train. (Host units

supplied by some manufacturers

have positive/negative logic

opposite to our logic. Reserve

the logic setting and try the

operation.)

[Refer to 3.3.4 [2] Format

Settings of Command Pulse

Train.]

5) Do not make the unit moving

distance less than the resolution

of the encoder. The actuator

does not move unless pulses by

the resolution of the encoder are

input.

[Refer to Caution in 3.3.4 [1]

Electrical Gear Setting]

(Note) In case of 3) or 4), the

actuator may not sometimes

operate smoothly.

You may not find case 5)

when the actuator is moved

for a long distance at a high

frequency.

(Note) Refer to 2.2.3 [3] PIO Circuit for PIO signal.