8.2.4 Impossible Communication

Situation

Possible cause

Check/Treatment

x

Not connectable with

host machine㩷

1) Communication rates do not match.

2) The machine number (station

number) is set to be duplicate with

that of another unit or out of the

range.

3) Parameter No.17 “Minimum delay

time for slave transmitter activation”

is set incorrectly.

4) Poor wiring or disconnection of

communication cable㩷

1) Set the communication rate to

match that of the host machine.

[Refer to the Instruction Manual

of the host unit.]

2) Correct the unit number

(station number) setting.

Machine numbers (station

numbers) vary depending on

communication modes. Refer to

the Instruction Manual of each

communication mode.

(Note 1)

3) Set the value in Parameter

No.17 smaller (2 as a

reference) if the response

timeout error is being issued in

the host system. In any other

cases, increase or decrease

the value at will to change the

send/receive timing. (If the

operation is performed

properly, the transmission cycle

of the host is too fast. Always

check the response of PCON

before next transmission.)

4) Review the wiring again. Check

if termination resistances are

connected to network terminals

with correct values.

(Note 1) Refer to the following Instruction Manual for communications:

x

RS485························ Section 9.1

x

DeviceNet ·················· Separate volume, DeviceNet Instruction Manual

x

CC-Link ······················ Separate volume, CC-Link Instruction Manual

x

PROFIBUS················· Separate volume, PROFIBUS-DP Instruction Manual

x

CompoNet·················· Separate volume, CompoNet Instruction Manual

x

MECHATROLINK······· Separate volume, MECHATROLINK Instruction Manual

x

EtherCAT ··················· Separate volume, EtherCAT Instruction Manual

x

EtherNet/IP ················ Separate volume, EtherNet/IP Instruction Manual

Advertising