Chapter 3 Operation

POWER CON

PCON-CA/CFA

80

[5] Zone Signal and Position Zone Signal (ZONE1,ZONE2, PZONE)

Output

PIO signal

ZONE1

ZONE2

(Note 2)

PZONE

(Note 2)

Pattern 0

{

{

{

Pattern 1

{

(Note 2)

×

{

Pattern 2

{

(Note 2)

×

{

Pattern 3

(Note 1)

Ч

Ч

Ч

Pattern 4

{

{

{

Pattern 5

{

{

{

{

: Available, u: Unavailable

Note 1 Pattern 3 does not have the zone signal output feature.

Note 2 In Parameter No.149 Zone Output Switchover, ZONE can be selected instead of

PZONE.

The relevant signal can be turned ON while the actuator passes or stops in the zone range in

either of the following 2 types:

1) Zone signal (ZONE1, ZONE2)····· The output signal is turned ON at the position set by the

proper parameter.

2) Position zone signal (PZONE)····· The output signal is turned ON at the position set in the

position table.

The feature can play a role as the sensor for judging whether the completion position is good or

not at completion of pressing, setting the continuous operation zone in pitch feed or interlocking

operations of other units in the setting zone.

(1) Zone signal (ZONE1, ZONE2)

Set the zone range to the relevant parameter.

1) Parameter No.1 : Zone boundary 1+

2) Parameter No.2 : Zone boundary 1-

3) Parameter No.23 : Zone boundary 2+

4) Parameter No.24 : Zone boundary 2-

The zone signal ZONE is kept effective also during the emergency stop unless the memory of

the origin is lost due to alarm.

Time

Velocity

Zone output signal

1)

2)

3)

4)

5)

1)

2)

3)

4) 5)