4 logic statement action editing – INFICON Cygnus Thin Film Deposition Controller User Manual

Page 97

Advertising
background image

4 - 13

IP

N 07

4-

37

9-

P1

K

Cygnus Operating Manual

TIMER HH:MM ### HH:MM

Sets the logic condition to be true when the designated timer ### reaches the
specified time HH:MM.

TIMER SECS ### sss.s

Sets the logic condition to be true when the designated Timer ### reaches the
specified time expressed in seconds, sss.s

XTAL FAIL ###

Sets the logic condition to be true as long as there is a Crystal Fail without
having a Crystal Switch for the designated channel ###. If 0 is selected it will
apply to any channel. The logic condition remains false if the XTAL FAIL
INHIBIT Action is active. The condition remains true until a working crystal is
input to the appropriate sensor.

4.4.2.4 Logic Statement Action Editing

Figure 4-8 Action Selection

Action Selection Display Function Keys

F1 REPLACE

Changes the Event or Action in reverse video to what is contained in the box
cursor.

F2 INSERT

Inserts the Event or Action in the box cursor into the Logic Statement at the
position indicated by reverse video. Previously entered Events or Actions are
moved to the right.

F6 STATEMENT

Exits the Event or Action List display and returns to the Logic Statement Editing
display.

Advertising