Figure 67. Metering Screen, Operation Tab

Tracking. One real-time metering field indicates the setpoint tracking error. Two status fields indicate the
on/off status for internal tracking and external tracking.

Bus. This real-time metering field displays the level of the bus voltage.

Start/Stop Mode. Two indicators show the start/stop mode status of the DECS-400. In Stop mode, the
Stop indicator changes from gray to green. In Start mode, the Start indicator changes from gray to red.
The Start/Stop button is clicked to toggle the DECS-400 start/stop mode status.

AVR/Manual Mode. AVR and Manual mode status is reported by two indicators. When the DECS-400 is
operating in AVR mode, the AVR indicator changes from gray to red. When operating in Manual mode,
the Manual indicator changes from gray to red. AVR mode or Manual mode is selected through the drop-
down menu.

FCR/FVR Mode. FCR and FVR mode status is reported by two indicators. When the DECS-400 is
operating in FCR mode, the FCR indicator changes from gray to red. When operating in FVR mode, the
FVR indicator changes from gray to red. FCR mode or FVR mode is selected through the drop-down
menu.

VAR/PF Mode. Three indicators report whether Var mode is active, Power Factor mode is active, or
neither mode is active. When Var mode is active, the VAR indicator changes from gray to red. When
Power Factor mode is active, the PF indicator changes from gray to red. When neither mode is active, the
Off indicator changes from gray to green. Var and Power Factor modes are enabled and disabled through
the drop-down menu.

Setpoint Pre-position. A control button and indicator is provided for the two setpoint pre-positions. Clicking
the Set 1 button adjusts the excitation setpoint to the pre-position 1 value and changes the Pre-position 1
indicator from gray to red. Clicking the Set 2 button adjusts the excitation setpoint to the pre-position 2
value and changes the Pre-position 2 indicator from gray to red.