Holding registers for relay parameters – Basler Electric DECS-400 User Manual

Page 237

Advertising
background image

9369700990 Rev R

225

Holding Registers for Exciter Diode Monitor Parameters

Table 44. Information Category C10—Exciter Diode Monitor Parameters

Registers

Data Description

Access

Data

Format

43376

Primary Number of Main Poles

RW

UINT16

43377

Primary Number of Exciter Poles

RW

UINT16

43378

Primary Open Diode Monitoring

RW

UINT16

43379

Primary Shorted Diode Monitoring

RW

UINT16

43380 to
43400

Not used

R

Not

Defined

43401

Primary Open Diode Pickup Level

RW

FLOAT

43403

Primary Shorted Diode Pickup Level

RW

FLOAT

43405

Primary Disable Open Diode Level

RW

FLOAT

43407

Primary Open Diode Detection Time Delay

RW

FLOAT

43409

Primary Shorted Diode Detection Time Delay

RW

FLOAT

43411

Primary Pole Ratio of Exciter Field to Main Field

RW

FLOAT

43413

Deadband - not used

RW

FLOAT

43415

Primary Open Diode Smoothing Filter Coefficient

RW

FLOAT

43417

Primary Shorted Diode Smoothing Filter Coefficient

RW

FLOAT

43419 to
43449

Not used

R

Not

Defined

43451

Secondary Number of Main Poles

RW

UINT16

43452

Secondary Number of Exciter Poles

RW

UINT16

43453

Secondary Open Diode Monitoring

RW

UINT16

43454

Secondary Shorted Diode Monitoring

RW

UINT16

43455 to
43475

Not used

R

Not

Defined

43476

Secondary Open Diode Pickup Level

RW

FLOAT

43478

Secondary Shorted Diode Pickup Level

RW

FLOAT

43480

Secondary Disable Open Diode Level

RW

FLOAT

43482

Secondary Open Diode Detection Time Delay

RW

FLOAT

43484

Secondary Shorted Diode Detection Time Delay

RW

FLOAT

43486

Secondary Pole Ratio of Exciter Field to Main Field

RW

FLOAT

43488

Deadband - not used

RW

FLOAT

43490

Secondary Open Diode Smoothing Filter Coefficient

RW

FLOAT

43492

Secondary Shorted Diode Smoothing Filter Coefficient

RW

FLOAT

Holding Registers for Relay Parameters

Table 45. Information Category C11—Relay Parameters

Registers

Data Description

Access

Data

Format

43526

Relay 1 State

RW

UINT16

43527

Relay 1 Contact Type

RW

UINT16

43528

Relay 1 Contact Status

RW

UINT16

43529

Relay 1 Momentary Time

RW

UINT16

43530 to
43575

Reserved for future C11 use

R

Not

Defined

43576

Relay 2 State

RW

UINT16

43577

Relay 2 Contact Type

RW

UINT16

43578

Relay 2 Contact Status

RW

UINT16

43579

Relay 2 Momentary Time

RW

UINT16

43580 to
43625

Reserved for future C11 use

R

Not

Defined

43626

Relay 3 State

RW

UINT16

43627

Relay 3 Contact Type

RW

UINT16

DECS-400

Modbus™ Communication