Traverse Rate

Range ............................................ 1 to 80 s
Increment ...................................... 0.1 s

Soft Start

Two sets of soft start settings are available when operating in AVR or FCR mode.

Soft Start Bias Level

Range ............................................ 0 to 90%
Increment ...................................... 1%

Soft Start Time Delay

Range ............................................ 1 to 7,200 s
Increment ...................................... 1 s

Sequence of Events Recording

Events are time- and date-stamped and stored in volatile memory.
Event Capacity .............................. 127
Scan Interval ................................. 50 ms
Logic Triggers……………………... Input state change, output state change, alarm annunciation, or system

operating status change

Data Logging (Oscillography)

Record Capacity ............................ 6
Variables per Record .................... 6
Sampling Rate ............................... 600 data points per record
Pre-Trigger Points ......................... Up to 599
Record Duration ............................ 2.4 s to 6,000 s
Interval ........................................... 4 ms to 10 s

Trending

Record Capacity ............................ 1
Variables per Record .................... 6
Sampling Rate ............................... 1,200 data points per record
Record Duration ............................ 1 hr to 30 d

Limiters

Underfrequency Compensation

Slope Adjustment Range .............. 0 to 0.3 PU
Knee Frequency Range ................ 15 to 90 Hz

Volts per Hertz

Slope Adjustment Range .............. 0 to 3 PU
Time Delay Range ........................ 0 to 10 s

DECS-400

Specifications