Programmable inputs, Terminals, Accessory input (remote setpoint control) – Basler Electric DECS-400 User Manual

Page 171: Voltage input, Current input, Control outputs, Voltage control output

Advertising
background image

9369700990 Rev R

159

Programmable Inputs

Any of the 10 programmable inputs can be configured, through the integrated programmable logic, with
the following functions.

2

nd

PID Settings Selection

2

nd

Pre-Position

Phase Rotation

Pre-Position

PSS Enable

PSS Motor/Generator Mode

PSS Parameters Set Selection

Reactive Differential Compensation Enable

Reactive Droop Compensation Enable

Secondary Enable

Speed Switch Enable

Unit/Parallel Operation (52 L/M)

Var/Power Factor Enable (52 J/K)

Terminals

Start ............................................... B1 (START), B2 (COM)
Stop ............................................... B3 (STOP), B2 (COM)
AVR ............................................... B4 (AVR), B5 (COM)
Manual ........................................... B6 (Man), B5 (COM)
Raise ............................................. B7 (RAISE), B8 (COM)
Lower ............................................. B9 (LOWER), B8 (COM)
Programmable 1 ............................ B10 (SW1), B11 (COM)
Programmable 2 ............................ B12 (SW2), B11 (COM)
Programmable 3 ............................ C23 (SW3), C24 (COM)
Programmable 4 ............................ C25 (SW4), C24 (COM)
Programmable 5 ............................ C26 (SW5), C27 (COM)
Programmable 6 ............................ C28 (SW6), C27 (COM)
Programmable 7 ............................ C29 (SW7), C30 (COM)
Programmable 8 ............................ C31 (SW8), C30 (COM)
Programmable 9 ............................ C32 (SW9), C33 (COM)
Programmable 10 .......................... C34 (SW10), C33 (COM)

Accessory Input (Remote Setpoint Control)

Voltage Input

Range ............................................ –10 Vdc to +10 Vdc
Terminals....................................... A16 (V+), A17 (V–)

Current Input

Range ............................................ 4 mAdc to 20 mAdc
Terminals....................................... A19 (I+), A20 (I–)

Control Outputs

The excitation setpoint is controlled by either an analog voltage output or analog current output.

Voltage Control Output

Range ............................................

±10 Vdc or 0 to +10 Vdc

Terminals....................................... D14 (VC+), D15 (RTNC)

DECS-400

Specifications