Holding registers for gain parameters – Basler Electric DECS-400 User Manual

Page 235

Advertising
background image

9369700990 Rev R

223

Registers

Data Description

Access

Data

Format

41855

Var limiter initial delay for secondary selection

RW

FLOAT

41856 to
42474

Reserved for future C7 use

R

Not

Defined

Note

Effective with firmware version 1.07, AVR and FCR have individual
gain settings. AVR gain settings are read/write with registers 42503
through 42507. FCR gain settings are read/write with registers 42553
through 42559. In versions prior to 1.07, gain settings for both AVR
and FCR are read/write with registers 42503, 42505, and 42507.

Holding Registers for Gain Parameters

Table 42. Information Category C8—Gain Parameters

Registers

Data Description

Access

Data

Format

42476

Active AVR/FCR Gain Setting Group

R

UINT16

42477 to
42500

Reserved for future C8 use

R

Not

Defined

42501

Primary Stability Range (Gain Table Index)

RW

FLOAT

42503

Primary AVR - Proportional Gain Kp

RW

FLOAT

42505

Primary AVR - Integral Gain Ki

RW

FLOAT

42507

Primary AVR - Derivative Gain Kd

RW

FLOAT

42509

OEL - Proportional Gain Kp

RW

FLOAT

42511

OEL - Integral Gain Ki

RW

FLOAT

42513

PF - Integral Gain Ki

RW

FLOAT

42515

VAR - Integral Gain Ki

RW

FLOAT

42517

FCR - Loop Gain Kg

RW

FLOAT

42519

Primary AVR - Loop Gain Kg

RW

FLOAT

42521

VAR - Loop Gain Kg

RW

FLOAT

42523

PF - Loop Gain Kg

RW

FLOAT

42525

OEL - Loop Gain Kg

RW

FLOAT

42527

UEL - Loop Gain Kg

RW

FLOAT

42529

Voltage Matching - Loop Gain Kg

RW

FLOAT

42531

Voltage Matching - Proportional Gain Kp

RW

FLOAT

42533

Voltage Matching - Integral Gain Ki

RW

FLOAT

42541

UEL - Proportional Gain Kp

RW

FLOAT

42543

UEL - Integral Gain Ki

RW

FLOAT

42545

Primary AVR - Derivative Time Constant Td

RW

FLOAT

42547

SCL - Loop Gain Kg

RW

FLOAT

42549

SCL - Proportional Gain Kp

RW

FLOAT

42551

SCL - Integral Gain Ki

RW

FLOAT

42553

FCR - Proportional Gain Kp

RW

FLOAT

42555

FCR - Integral Gain Ki

RW

FLOAT

42557

FCR - Derivative Gain Kd

RW

FLOAT

42559

Primary FCR - Derivative Time Constant Td

RW

FLOAT

42561

FVR Proportional Gain Kp

RW

FLOAT

42563

FVR Integral Gain Ki

RW

FLOAT

42565

FVR Derivative Gain Kd

RW

FLOAT

42567

FVR Derivative Time Constant Td Gain

RW

FLOAT

42569

FVR Loop Gain Kg

RW

FLOAT

42570 to

Reserved for future C8 use

R

Not

DECS-400

Modbus™ Communication

Advertising