Decs-400 modbus™ register space, Decs-400 modbus ™ register space – Basler Electric DECS-400 User Manual

Page 224

Advertising
background image

212

9369700990 Rev R

exclusive-ORed with the fixed polynomial value A001 (hex) prior to the next shift. Once all bytes of the
message have undergone the above algorithm, the CRC register will contain the message CRC value to
be placed in the error check field.

DECS-400 Modbus

™ Register Space

Modbus address space from 40000 to 49999 refers to function codes 3, 6, and 16. The DECS-400 uses
address space from 40001 to 44999 (4,999 registers). This address space is divided into 14 areas,
referred to as information categories.

Table 34 provides a statistical summary for each information category.

Table 34. Information Category Summary

Information

Category ID

Information

Category

Total # of
Reserved

Holding

Registers

Holding

Register
Address

Space

Number

of Used

Registers

Access

Privilege

Data Types

Mapped to

Registers

(Total # of
Variables)

C1

Version Data

200

40001 to
40200

60

R

UINT8

C2

Metering,
Group 1

199

40201 to
40399

61

R

UINT16: 11
FLOAT: 50

C3

System
Configuration

199

40401 to
40599

40

RW: 39
R: 1

UINT16: 11
FLOAT: 29

C4

Operating
Mode
Parameters

97

40604 to
40700

45

RW: 23
R: 22

UINT: 45

C5

Setpoint
Parameters

449

40701 to
41149

58

RW: 34
R: 24

UINT16: 8
FLOAT: 50

C6

Startup
Parameters

199

41151 to
41349

17

RW: 16
R: 1

FLOAT: 16
UINT16: 1

C7

Limiter
Parameters

1,124

41351 to
42474

68

RW: 65
R: 3

FLOAT: 62
UINT16: 6

C8

Gain Registers

524

42476 to
42999

33

RW: 32
R: 1

UINT16: 1
FLOAT: 32

C9

Protection
Function
Parameters

127

43001 to
43127

29

RW: 23
R: 6

UINT16: 13
FLOAT: 16

C10

Exciter Diode
Monitor
Parameters

149

43376 to
43492

26

RW

UINT16: 8
FLOAT: 18

C11

Relay
Parameters

600

43526 to
44125

24

RW

UINT16

C12

ASCII and
Modbus
Communication
Parameters

125

44126 to
44250

16

RW: 14
R: 2

UINT8: 2
UINT14: 6

C13

Metering,
Group 2

50

44201 to
44250

3

RW

UINT16

C14

PSS
Parameters

749

44251 to
44999

91

RW: 89
R: 2

UINT16: 23
FLOAT: 68

Modbus™ Communication

DECS-400

Advertising