Human-Machine Interface

This chapter describes the DECS-400 human-machine interface (HMI) and illustrates navigation of the
menu tree accessed through the front panel and LCD.

Controls and Indicators

DECS-400 controls and indicators are illustrated in Figure 2 and described in Table 1. The locators and
descriptions of Table 1 correspond to the locators shown in Figure 2.

Figure 2. Controls and Indicators

Table 1. Control and Indicator Descriptions

Locator

Description

A

Null Balance Indicator. This LED lights when the setpoint of the inactive operating
modes (AVR, FCR, Var, or Power Factor) match the setpoint of the active mode.

B

PSS Active Indicator. This LED lights when the integrated power system stabilizer is
enabled and can generate a stabilizing signal in response to a power system
disturbance.

C

Pre-Position Indicator. This LED lights when the setpoint of the active operating mode is
at either of the two pre-position setting levels.

D

Lower Limit Indicator. This LED lights when the setpoint of the active operating mode is
decreased to the lower setpoint limit.

E

Upper Limit Indicator. This LED lights when the setpoint of the active operating mode is
increased to the upper setpoint limit.

F

Latch. Two lever-style latches (locators F and M) secure the DECS-400 draw-out
assembly in its case. A captive Phillips screw in each latch can be tightened to lock the
draw-out assembly in place.

G

Communication Port. This RS-232 port has a female DB-9 connector for local
communication with a PC operating BESTCOMS software (supplied with the DECS-
400).

DECS-400

Human-Machine Interface