Table 12 – Basler Electric DECS-400 User Manual

Page 141

Advertising
background image

9369700990 Rev R

129

Table 12. Contact Input Terminals

Terminal

Description

B1 (START)

∗ Positive terminal of Start contact input

B2 (COM)

Common terminal of Start and Stop contact inputs

B3 (STOP)

Positive terminal of Stop contact input

B4 (AVR)

Positive terminal of AVR contact input

B5 (COM)

Common terminal of AVR and FCR contact inputs

B6 (MAN)

Positive terminal of Manual contact input

B7 (RAISE) †

Positive terminal of Raise contact input

B8 (COM)

Common terminal of Raise and Lower contact inputs

B9 (LOWER) † Positive terminal of Lower contact input

B10 (SW1)

Positive terminal of programmable contact input #1

B11 (COM)

Common terminal of programmable contact inputs #1 and #2

B12 (SW2)

Positive terminal of programmable contact input #2

C23 (SW3)

Positive terminal of programmable contact input #3

C24 (COM)

Common terminal of programmable contact inputs #3 and #4

C25 (SW4)

Positive terminal of programmable contact input #4

C26 (SW5)

Positive terminal of programmable contact input #5

C27 (COM)

Common terminal of programmable contact inputs #5 and #6

C28 (SW6)

Positive terminal of programmable contact input #6

C29 (SW7)

Positive terminal of programmable contact input #7

C30 (COM)

Common terminal of programmable contact inputs #7 and #8

C31 (SW8)

Positive terminal of programmable contact input #8

C32 (SW9)

Positive terminal of programmable contact input #9

C33 (COM)

Common terminal of programmable contact inputs #9 and #10

C34 (SW10)

Positive terminal of programmable contact input #10

∗ Functions are activated by a momentary input.

† Functions are active only when the corresponding contact input is active.

Field Voltage and Current

Field voltage and current signals are supplied to connector P1 of the DECS-400 by the Field Isolation
Module. A cable, supplied with the Field Isolation Module, connects from Field Isolation Module connector
J1 to DECS-400 connector P1.

IRIG

The clock function of the DECS-400 is synchronized with a time code source through the application of a
standard IRIG-B signal to the IRIG terminals. Refer to the Specifications chapter for specifications
pertaining to the IRIG input. Table 13 lists the IRIG terminals.

Table 13. IRIG Terminals

Terminal

Description

D1 (IRIG+)

Positive IRIG terminal

D2 (IRIG–)

Negative IRIG terminal

DECS-400

Installation