High generator voltage (in avr mode), Generator voltage unstable (hunting), Poor voltage regulation – Basler Electric DECS-400 User Manual

Page 163: No buildup in fcr mode, No control signal at firing circuit input, Limiters do not limit at the desired level, Poor reactive control, Protection or limit annunciation, Metering readings incorrect, No communication

Advertising
background image

9369700990 Rev R

151

High Generator Voltage (In AVR Mode)

Check the for the following settings:

a.

AVR voltage setpoint

b.

AVR Kg loop gain (too high)

c.

Generator potential transformer (PT) primary voltage

d.

Generator PT secondary voltage

e.

Accessory inputs (should be zero)

f.

Var/PF and droop should be disabled

If the problem persists, contact Basler Electric Technical Sales Support for advice.

Generator Voltage Unstable (Hunting)

Verify that the exciter power converter is working correctly by substituting the appropriate battery voltage
in place of the DECS-400 drive voltage. If the problem is caused by the DECS-400, check the gain
settings for the specific mode of operation selected.

If the problem persists, contact Basler Electric Technical Sales Support for advice.

Poor Voltage Regulation

Poor voltage regulation may result from insufficient K

g

loop gain. Increase the AVR loop gain accordingly.

No Buildup in FCR Mode

Low K

g

loop gain may hinder buildup when operating in FCR mode. An FCR loop gain of 150 or greater

may be necessary.

No Control Signal at Firing Circuit Input

Check the control signal setting and output of the DECS-400. Depending on the signal selected, the
DECS-400 will produce a 0 to 10 Vdc, 4 to 20 mAdc, or –10 to +10 Vdc control signal.

Limiters Do Not Limit at the Desired Level

Insufficient K

g

loop gain for the limiters may hinder limiter operation. Increase the limiter loop gain

accordingly.

Poor Reactive Control

Poor reactive control may result if the AVR droop setting is too low. Adjust the AVR droop accordingly.

Protection or Limit Annunciation

If a protection function or limiting function is annunciated, check the associated setting values.

If the problem persists, contact Basler Electric Technical Sales Support for advice.

Metering Readings Incorrect

If your PF, var, or watt readings are significantly different from the expected readings for a known load,
verify that the CT for phase B is actually placed on the phase B input to the DECS-400 and not or phase
A or C.

No Communication

If communication cannot be initialized, check the serial cables to the port connections, the transmission
speed (baud rate), and supporting software.

Real-Time Clock Information Lost After Loss of Control Power

A loss of real-time clock information indicates a depleted backup battery. See Backup Battery
Replacement
for the battery replacement procedure.

DECS-400

Maintenance

Advertising