Holding registers for startup parameters – Basler Electric DECS-400 User Manual

Page 232

Advertising
background image

220

9369700990 Rev R

Registers

Data Description

Access

Data

Format

40839

Step size for PF mode setpoint's adjustable maximum (in % of rated field
current) = .005

R

FLOAT

40841

FCR mode setpoint pre-position 2; adjustment range is determined by
registers (40761-62) and (40769-70)

RW

FLOAT

40843

AVR mode setpoint pre-position 2; adjustment range is determined by
registers (40763-64) and (40771-72)

RW

FLOAT

40845

VAR mode setpoint pre-position 2; adjustment range is determined by
registers (40765-66) and (40773-74)

RW

FLOAT

40847

PF mode setpoint pre-position 2; adjustment range is determined by
registers (40767-68) and (40775-76)

RW

FLOAT

40849

Line Drop Compensation Setpoint, adjustable from 0 to 30% in .1%
increments

RW

FLOAT

40851

FVR mode setpoint (in volts). Adjustment range is determined by registers
40853-54 and 40855-56

RW

FLOAT

40853

FVR maximum setpoint (in volts). Equal to % of nominal x rated field
voltage (Registers 40863-64 x 40477-78

÷ 100)

R

FLOAT

40855

FVR maximum setpoint (in volts). Equal to % of nominal x rated field
voltage (Registers 40865-66 x 40477-78

÷ 100)

R

FLOAT

40857

FVR mode traverse rate, adjustable from 10 to 200 seconds in 1 second
increments

RW

FLOAT

40859

FVR mode setpoint pre-position 1 adjustment range. Determined by
registers (40853-54) and (40855-56)

RW

FLOAT

40861

FVR mode setpoint step size. =setpoint range

÷ (traverse rate x 10):[regs.

40855-56) –regs. 40853-54)]

÷[(regs. 40857-58) x 10]

R

FLOAT

40863

FVR mode setpoint minimum (in % of rated field voltage), adjustable from 0
to 100% in 0.1% increments

RW

FLOAT

40865

FVR mode setpoint maximum (in % of rated field voltage), adjustable from
100 to 120% in 0.1% increments

RW

FLOAT

40867

Minimum value for FVR mode setpoint’s adjustable minimum (in % of rated
field voltage) =0%

R

FLOAT

40869

Maximum value for FVR mode setpoint’s adjustable maximum (in % of
rated field voltage) = 120%

R

FLOAT

40871

Step size for FVR mode setpoint’s adjustable maximum (in % of rated field
voltage) = 0.1%

R

FLOAT

40873

FVR mode setpoint pre-position 2: adjustment range is determined by
registers (40853-54) and (40855-56)

RW

FLOAT

Holding Registers for Startup Parameters

Table 40. Information Category C6—Startup Parameters

Registers

Data Description

Access

Data

Format

41151

Active Startup Setting Group

R

UINT16

41153

PSS Power Level Enable

R

UINT16

41154 to
41170

Not used

R

Not

Defined

41171

Primary Generator Voltage Soft Start Bias

RW

FLOAT

41173

Primary Generator Voltage Soft Start Time

RW

FLOAT

41175

Underfrequency Setting (Corner Frequency)

RW

FLOAT

41177

V/Hz High Setting

RW

FLOAT

41179

V/Hz Low Setting

RW

FLOAT

41181

V/Hz Time Setting

RW

FLOAT

41183

Voltage Matching Band

RW

FLOAT

41185

Voltage Matching Level (Generator to Bus)

RW

FLOAT

41187

Fine Voltage Adjust Band

RW

FLOAT

41189

Loss of Sensing Time Delay

RW

FLOAT

Modbus™ Communication