Basler Electric DECS-400 User Manual

Page 198

Advertising
background image

186

9369700990 Rev R

=====> DESTINATION: Layer2

InputBuffer.Contact Switch 3 ---> Mux1.Input
Layer1.Not2.Output ---> Mux2.Input
Layer1.Or3.Output ---> Mux3.Input
Layer2.Mux3.Output2 ---> Or1.Input1
Layer2.Or1.Output ---> Or2.Input1
Layer1.Or4.Output ---> Or2.Input2
Layer1.Or5.Output ---> Or2.Input3
Layer1.Or6.Output ---> Or2.Input4
Layer2.Mux1.Output1 ---> Not1.Input
Layer2.Mux1.Output3 ---> Not2.Input

=====> DESTINATION: Layer3

Layer2.Not2.Output ---> And1.Input1
InputBuffer.Contact Switch 9 ---> And1.Input2
InputBuffer.Volts per Hz Limit ---> Or1.Input1
InputBuffer.Field Over Current ---> Or1.Input2

=====> DESTINATION: Layer4

Layer3.Or1.Output ---> Mux1.Input

=====> DESTINATION: OutputBuffer

InputBuffer.Start ---> Start
InputBuffer.Stop ---> Stop
Layer2.Not1.Output ---> Parallel
InputBuffer.Contact Switch 2 ---> Pre Position 2
InputBuffer.AVR ---> AVR
InputBuffer.FCR ---> FCR
Layer2.Mux1.Output2 ---> Pre Position 1
InputBuffer.Raise ---> Raise
InputBuffer.Lower ---> Lower
Layer3.And1.Output ---> PF Var
InputBuffer.Contact Switch 8 ---> Dual PID Selection
InputBuffer.Contact Switch 1 ---> Alarm Reset
Layer1.Not3.Output ---> Voltage Matching
InputBuffer.Contact Switch 6 ---> Secondary Protect
Layer1.Not4.Output ---> Loss of Sensing Transfer to FCR
Layer1.Mux2.Output1 ---> Secondary OEL
Layer1.Mux2.Output2 ---> Secondary UEL
Layer1.Mux2.Output3 ---> Secondary SCL
InputBuffer.Contact Switch 7 ---> Secondary Soft Start
Layer1.Mux1.Output1 ---> OEL Off-Line/On-Line Option
Layer2.Mux2.Output1 ---> Modbus Write
Layer2.Mux2.Output2 ---> Modem Write
InputBuffer.FCR Mode ---> Relay Output 1
Layer2.Or2.Output ---> Relay Output 2
Layer2.Mux3.Output1 ---> Relay Output 3
Layer1.Mux4.Output2 ---> Relay Output 4
InputBuffer.Field Flashing ---> Relay Output 5
Layer4.Mux1.Output1 ---> Relay Output 5
Layer4.Mux1.Output2 ---> Relay Output 6

Programmable Logic

DECS-400