Data Logging

The data logging function of the DECS-400 can record up to six oscillography records. DECS-400
oscillography records use the IEEE Standard Common Format for Transient Data Exchange
(COMTRADE). Each record is time- and date-stamped. After six records have been recorded, the DECS-
400 begins recording the next record over the oldest record. Because all oscillography records are stored
in volatile memory, all records are lost if DECS-400 operating power is interrupted.

Each oscillography record can consist of up to six user-selectable variables with up to 600 data points
recorded for each variable. The interval between records is adjustable from 4 milliseconds to 10 seconds.

Data points may be selected for pre-trigger operation in order to capture events prior to a fault. Up to 599
pre-trigger data points may be selected. Data points not designated for pre-trigger recording are assigned
to the post-trigger portion of the fault record. This feature, combined with the adjustable sample rate,
allows for flexible data sampling around the fault.

A maximum of six variables may be selected to trigger a sequence of events record. The available
variables are listed below.

Auxiliary Voltage Input

AVR PID Error Signal Input

Bus Frequency

Bus Voltage

Compensated Frequency Deviation

Control Output

Cross Current Input

Field Current

Field Voltage

Frequency Response

Generator Average Current

Generator Average Voltage

Generator Frequency

Generator Ia

Generator Ib

Generator Ic

Generator kVA

Generator kvar

Generator kW

Generator Power Factor

Generator Vab

Generator Vbc

Generator Vca

Negative Sequence Current

Negative Sequence Voltage

Overexcitation Controller Output

PF Mode Output

Phase Angle Ia - Vca

Phase Angle Iaux - Vca

Phase Angle Ib - Vca

Phase Angle Ic - Vca

Phase Angle Vab

Phase Angle Vbc

PID Integrator State

Positive Sequence Current

Positive Sequence Voltage

PSS Electrical Power

PSS Filtered Mechanical Power

PSS Final Output

PSS Lead-Lag #1

PSS Lead-Lag #2

PSS Lead-Lag #3

PSS Lead-Lag #4

PSS Mechanical Power

PSS Mechanical Power LP #1

PSS Mechanical Power LP #2

PSS Mechanical Power LP #3

PSS Mechanical Power LP #4

PSS Post-Limit Output

PSS Power HP #1

PSS Pre-Limit Output

PSS Speed HP #1

PSS Synthesized Speed

PSS Terminal Voltage

PSS Torsional Filter #1

PSS Torsional Filter #2

PSS Washed Out Power

PSS Washed Out Speed

Stator Current Limiter Output

Terminal Frequency Deviation

Time Response

Underexcitation Controller Output

DECS-400

Functional Description