Data Logging

The data logging function of the DECS-400 can record up to six oscillography records. DECS-400
oscillography records use the IEEE Standard Common Format for Transient Data Exchange
(COMTRADE). Each record is time- and date-stamped. After six records have been recorded, the DECS-
400 begins recording the next record over the oldest record. Because all oscillography records are stored
in volatile memory, all records are lost if DECS-400 operating power is interrupted.

Each oscillography record can consist of up to six user-selectable variables with up to 600 data points
recorded for each variable. The interval between records is adjustable from 4 milliseconds to 10 seconds.

Data points may be selected for pre-trigger operation in order to capture events prior to a fault. Up to 599
pre-trigger data points may be selected. Data points not designated for pre-trigger recording are assigned
to the post-trigger portion of the fault record. This feature, combined with the adjustable sample rate,
allows for flexible data sampling around the fault.

A maximum of six variables may be selected to trigger a sequence of events record. The available
variables are listed below.

•

Auxiliary Voltage Input

•

AVR PID Error Signal Input

•

Bus Frequency

•

Bus Voltage

•

Compensated Frequency Deviation

•

Control Output

•

Cross Current Input

•

Field Current

•

Field Voltage

•

Frequency Response

•

Generator Average Current

•

Generator Average Voltage

•

Generator Frequency

•

Generator Ia

•

Generator Ib

•

Generator Ic

•

Generator kVA

•

Generator kvar

•

Generator kW

•

Generator Power Factor

•

Generator Vab

•

Generator Vbc

•

Generator Vca

•

Negative Sequence Current

•

Negative Sequence Voltage

•

Overexcitation Controller Output

•

PF Mode Output

•

Phase Angle Ia - Vca

•

Phase Angle Iaux - Vca

•

Phase Angle Ib - Vca

•

Phase Angle Ic - Vca

•

Phase Angle Vab

•

Phase Angle Vbc

•

PID Integrator State

•

Positive Sequence Current

•

Positive Sequence Voltage

•

PSS Electrical Power

•

PSS Filtered Mechanical Power

•

PSS Final Output

•

PSS Lead-Lag #1

•

PSS Lead-Lag #2

•

PSS Lead-Lag #3

•

PSS Lead-Lag #4

•

PSS Mechanical Power

•

PSS Mechanical Power LP #1

•

PSS Mechanical Power LP #2

•

PSS Mechanical Power LP #3

•

PSS Mechanical Power LP #4

•

PSS Post-Limit Output

•

PSS Power HP #1

•

PSS Pre-Limit Output

•

PSS Speed HP #1

•

PSS Synthesized Speed

•

PSS Terminal Voltage

•

PSS Torsional Filter #1

•

PSS Torsional Filter #2

•

PSS Washed Out Power

•

PSS Washed Out Speed

•

Stator Current Limiter Output

•

Terminal Frequency Deviation

•

Time Response

•

Underexcitation Controller Output

DECS-400

Functional Description