Holding registers for metering, group 1 – Basler Electric DECS-400 User Manual

Page 226

Advertising
background image

214

9369700990 Rev R

Registers

Data Description

Access

Data

Format

40045

2nd character of the boot program version

R

UINT8

40046

3rd character of the boot program version

R

UINT8

40047

4th character of the boot program version

R

UINT8

40048

5th character of the boot program version

R

UINT8

40049

6th character of the boot program version

R

UINT8

40050

7th character of the boot program version

R

UINT8

40051

Last character of the boot program version

R

UINT8

40052

1st character of the boot program date

R

UINT8

40053

2nd character of the boot program date

R

UINT8

40054

3rd character of the boot program date

R

UINT8

40055

4th character of the boot program date

R

UINT8

40056

5th character of the boot program date

R

UINT8

40057

6th character of the boot program date

R

UINT8

40058

7th character of the boot program date

R

UINT8

40059

8th character of the boot program date

R

UINT8

40060

Last character of the boot program date

R

UINT8

40061 to
40200

Reserved for future C1 data

R

Not

Defined

Holding Registers for Metering, Group 1

Table 36. Information Category C2—Metering, Group 1

Registers

Data Description

Access

Data

Format

40201

Leading/lagging load indicator 0 = leading load, 1 = lagging load

R

UINT16

40202

Motoring/generating indicator 0 = motoring, 1 = generating

R

UINT16

40203

Status of front panel LEDs (bit flags where 0 = off and 1 = on)
b0 = null balance, b1 = PSS active, b2 = pre-position, b3 = upper limit,
b4 = lower limit, b5 = edit, b6-b15 = unassigned

R

UINT16

40204

Contact input states: b0 = start, b1 = stop, b2 = auto, b3 = manual, b4 =
raise, b5 = lower, b6 = sw1, b7 = sw2, b8 = sw3, b9 = sw4, b10 = sw5,
b11 = sw6, b12 = sw7, b13 = sw8, b14 = sw9, b15 = sw10

R

UINT16

40205

Voltage matching status indicator

R

UINT16

40206

Adjustment range, in percent, of the active setpoint

R

UINT16

40207

Annunciation status bit flags (0 = clear and 1 = annunciation is present)
b0 = field overvoltage, b1 = field overcurrent, b2 = generator undervoltage,
b3 = generator overvoltage, b4 = underfrequency, b5 = in OEL, b6 = in
UEL, b7 = in FCR mode, b8 = no sensing, b9 = setpoint lower limit, b10 =
setpoint upper limit, b11 = generator failed to build up, b12 = generator
below 10 Hz, b13 = field overtemperature, b14 = EDM open diode, b15 =
EDM shorted diode

R

UINT16

40208

Annunciation status bit flags (0 = clear and 1 = annunciation is present)
b0 = loss of field, b1 = in SCL, b2 = V/Hz, b3 = loss of FIT, b4 = power
low, b5 = PSS V unbalance, b6 = PSS I unbalance, b7 = PSS power
below threshold, b8 = PSS speed failure, b9 = PSS voltage limit, b10 =
clock reset, b11 = loss of IRIG, b12-b15 = unassigned

R

UINT16

40209

Protection status bit flags (0 = clear and 1 = status present)
b0 = field overvoltage, b1 = field overcurrent, b2 = generator undervoltage,
b3 = generator overvoltage, b4 = underfrequency, b5 = in OEL, b6 = in
UEL, b7 = in FCR mode, b8 = no sensing, b9 = setpoint lower limit, b10 =
setpoint upper limit, b11 = generator failed to build up, b12 = generator
below 10 Hz, b13 = field overtemperature, b14 = EDM open diode, b15 =
EDM shorted diode

R

UINT16

40210

Protection status bit flags (0 = clear and 1 = status present)
B0 = loss of field, b1 = in SCL, b2 = V/Hz, b3 = loss of FIT, b4 = power
low, b5 = PSS V unbalance, b6 = PSS I unbalance, b7 = PSS power
below threshold, b8 = PSS speed failure, b9 = PSS voltage limit, b10 =
clock reset, b11 = loss of IRIG, b12-b15 = unassigned

R

UINT16

Modbus™ Communication

DECS-400