Alarms message – Basler Electric DECS-400 User Manual

Page 36

Advertising
background image

24

9369700990 Rev R

Alarms Message

The alarms message line remains blank during normal operating conditions. If an enunciable condition
occurs, “ALARMS (PRESS < OR >)” is displayed. Information about the condition is obtained by viewing
the alarm message screen.

Alarm Message Screen

Pressing either the left or right scrolling pushbuttons, while viewing the metering screen, displays the
alarm message screen. This screen displays up to six messages identifying the conditions that led to the
most recent annunciations.

lists the annunciations that may appear on the alarm message screen. When more than one message is
listed, the newest messages are added to the bottom of the list. Once the list contains six messages, any
further annunciations will cause the oldest message to be deleted from the top of the list.

Table 5. Alarm Messages

Annunciation Message

Duration of Message

CLOCK RESET

Maintained until reset

CURRENT UNBALANCE

Automatically reset

EXCESSIVE V/HZ

Maintained until reset

EXCITER DIODE OPEN

Maintained until reset

EXCITER DIODE SHORT

Maintained until reset

FAILED TO BUILD UP

Maintained until reset

FIELD OVER TEMP

Maintained until reset

FIELD OVERCURRENT

Maintained until reset

FIELD OVERVOLTAGE

Maintained until reset

GEN. OVERVOLTAGE

Maintained until reset

GEN. UNDERVOLTAGE

Maintained until reset

LOSS ISOLATION MODULE

Automatically reset

LOSS OF FIELD

Maintained until reset

LOSS OF IRIG

Automatically reset

LOST VOLTAGE SENSING

Maintained until reset

OVEREXCITATION LIMIT

Clears 2 s after end of event

POWER BELOW THRESHOLD

Automatically reset

POWER SUPPLY LOW

Automatically reset

PSS BLOCK

Automatically reset

SPEED FAILURE

Automatically reset

STATOR CURRENT LIMIT

Clears 2 s after end of event

SYSTEM BELOW 10 HZ

Clears 2 s after end of event

UNDEREXCITATION LIMIT

Clears 2 s after end of event

UNDERFREQUENCY

Clears 2 s after end of event

VAR LIMIT

Automatically reset

VOLTAGE LIMIT

Automatically reset

VOLTAGE UNBALANCE

Automatically reset

The list of alarm messages can be cleared by pressing the Reset pushbutton. Pressing the Reset
pushbutton also sends the display back to the metering screen and clears the metering screen alarms

Human-Machine Interface

DECS-400