Firmware installation procedure – Basler Electric DECS-400 User Manual

Page 165

Advertising
background image

9369700990 Rev R

153

install the firmware. Firmware files may be supplied as an email message file attachment, a file
downloaded from the Basler Electric website, or on a firmware update CD-ROM.

Firmware Installation Procedure

The following conventions are used in this procedure:

Italic text marks the menu commands and submenu commands that are to be clicked

Bold text marks the buttons that are to be clicked

If you have difficulty installing the firmware, contact Basler Electric for assistance.

Caution

Some firmware upgrades require the reassignment and re-landing of
some wire terminations due to features that may be added, changed
or removed. Contact Basler Electric and ask about any hardware or
system changes that will need to be performed before installing new
firmware. Serious damage to the DECS or your system could result if
these changes are not completed first.

Note

In the course of upgrading firmware, the DECS-400 will reboot several
times. This may cause the DECS to give a Watchdog Failure alarm
and, depending on your fault tripping scheme, may trip your
generator’s lockout relay. It is recommended that firmware upgrades
be done while the prime mover is stopped for maintenance.

1.

Start BESTCOMS and connect to the DECS unit.

a.

Communications

b.

Connect

c.

RS232-COM0

d.

Select the communications port of the host PC.

e.

Click Connect

f.

Type the password for your unit and press Enter or click OK.

g.

Wait for the currently installed settings to load from the DECS into BESTCOMS.

2.

Take note of the DECS serial port speed.

a.

Communications

b.

Configure

c.

Make note of the baud rate listed under “Com0 RS-232”.

d.

Click OK when finished.

3.

Save the settings to your hard drive.

a.

Click the disk icon (

).

b.

Select a location that you can find again later (e.g., c:\Windows\desktop).

c.

Select an appropriate file name.

d.

Click Save

4.

Print the settings to a text file.

a.

File

b.

Printing

DECS-400

Maintenance

Advertising