Specifications, Operating power, Ac input (style xcxx only) – Basler Electric DECS-400 User Manual

Page 169: Dc input (style xcxx, xlxx), Generator voltage sensing, 50 hertz sensing, 60 hertz sensing, Bus voltage sensing

Advertising
background image

9369700990 Rev R

157

Specifications

DECS-400 electrical and physical specifications are listed in the following paragraphs.

Operating Power

AC Input (Style XCXX Only)

Nominal ......................................... 120 Vac
Range ............................................ 82 to 132 Vac
Frequency ..................................... 50/60 Hz
Burden ........................................... 50 VA
Terminals....................................... C2 (N), C3 (L)

DC Input (Style XCXX, XLXX)

Nominal

Style XCXX ............................. 125 Vdc

Style XLXX .............................. 24/48 Vdc

Range

Style XCXX

90 to 150 Vdc

Style XLXX

16 to 60 Vdc

Burden ........................................... 30 W
Terminals....................................... C4 (BATT–), C5 (BATT+)

Generator Voltage Sensing

Configuration ................................. 1-phase (A-phase (E1) to C-phase (E3)) or 3-phase
Ranges .......................................... 120 V or 240 V, automatically selected
Burden ........................................... <1 VA
Terminals....................................... A9, (E1), A10 (E2), A11 (E3)

50 Hertz Sensing

Range 1 ......................................... 85 to 127 Vac
Range 2 ......................................... 170 to 254 Vac

60 Hertz Sensing

Range 1 ......................................... 94 to 153 Vac
Range 2 ......................................... 187 to 305 Vac

Bus Voltage Sensing

Configuration ................................. 1-phase (A-phase (BUS1) to C-phase (BUS3))
Ranges .......................................... 120 V or 240 V, automatically selected
Burden ........................................... <1 VA
Terminals....................................... A13 (BUS1), A14 (BUS3)

50 Hertz Sensing

Range 1 ......................................... 85 to 127 Vac
Range 2 ......................................... 170 to 254 Vac

60 Hertz Sensing

Range 1 ......................................... 94 to 153 Vac
Range 2 ......................................... 187 to 305 Vac

DECS-400