Volts per hertz (24), Exciter diode failure, Type tests – Basler Electric DECS-400 User Manual

Page 178: Agency certifications, Gost-r, Niipt, Real-time clock battery

Advertising
background image

166

9369700990 Rev R

Volts per Hertz (24)

Setting Range ............................... 0.5 to 6 V/Hz
Integrating Reset Range ............... 0 to 9.9 V/Hz

Exciter Diode Failure

Exciter to Stator Poles Ratio ......... 1 to 10 (0 if unknown)
Ripple Threshold, Open/Shorted .. 0 to 100%, in 0.1% increments
Time Delay Open .......................... 10 to 60 s, in 0.1 increments
Time Delay Shorted ...................... 5 to 30 s, in 0.1 increments
Open/Shorted Inhibit Levels .......... 0 to 100%, in 0.1% increments
Generator Frequency Range ........ 40 to 70 Hz

Type Tests

Shock ............................................ IEC 60255-21-2
Vibration ........................................ IEC 60255-21-1
Humidity ........................................ IEC 68-1, IEC 68-2-28
Dielectric Strength ......................... IEEE 421.3
Transients...................................... IEEE C37.90.1-1989
Surge Withstand Capability ........... IEEE C37.90.1-1989
Impulse .......................................... IEC 60255-5
Electrostatic Discharge ................. IEEE C37.90.3 Draft 2.3
Radio Frequency Interference....... IEEE C37.90.2

Agency Certifications

UL

UL recognized per UL Standard 508, File E97035 and CSA Standard C22.2 No. 14

CE

Meets or exceeds the standards required for distribution in the European community.

GOST-R

GOST-R certified per the relevant standards of Gosstandart of Russia.

NIIPT

NIIPT, JSC Russian certification.

Real-Time Clock Battery

Type .............................................. Lithium, ½ AA size
Rating ............................................ 3.6 Vdc, 1.0 Ah nominal capacity
Replacement Interval .................... 5 yr
Part Number .................................. Basler Electric 37819

Tadiran TL-2150/S

Specifications

DECS-400

Advertising