Holding registers for operating mode parameters – Basler Electric DECS-400 User Manual

Page 229

Advertising
background image

9369700990 Rev R

217

Holding Registers for Operating Mode Parameters

Table 38. Information Category C4—Operating Mode Parameters

Registers

Data Description

Access

Data

Format

40601

Virtual toggle switch for changing unit mode from stop to start. Value 1 is
only valid to apply. Reading this register provides the status: 0=STOP,
1=START.

RW

UINT16

40602

Virtual toggle switch for changing control from AVR mode to Manual mode.
Value of 1 is the only valid value to apply. Reading this register provides the
control mode status: 0=base mode, 1=manual, 2=AVR.

RW

UINT16

40603

Virtual toggle switch for changing operation between unit and parallel.
Value 1 is only valid to apply. Read value of register is aloways 0.

RW

UINT16

40604

PF/Var Enabled 0=off, 1=PF, 2=var

RW

UINT16

40605

Internal Tracking Enabled

RW

UINT16

40606

Pre-position 1 Enabled

RW

UINT16

40607

Raise Enabled

RW

UINT16

40608

Lower Enabled

RW

UINT16

40609

LimiterMode; 0=off, 1=UEL, 2=OEL, 3=UEL&OEL, 4=SCL, 5=UEL&SCL,
6=OEL&SCL, 7=UEL&OEL&SCL, 8=VARL, 9=VARL&OEL,
10=VARL&OEL, 11=VARL&OEL&UEL, 12=VARL&SCL,
13=VARL&SCL&OEL, 14=VARL&SCL&OEL, 15=VARL&SCL&UEL&OEL

RW

UINT16

40610

Voltage Matching Mode (0=off, 1=on)

R

UINT16

40611

Operating Mode (0=off, 1=PF, 2=var)

R

UINT16

40612

Unit mode where 0=stop, 1=start

R

UINT16

40613

Control Mode (1 = Manual, 2 = AVR)

R

UINT16

40614

Internal Tracking Enabled

R

UINT16

40615

Pre-position Enabled

R

UINT16

40616

Auto Transfer Enabled

R

UINT16

40617

Load Comp Mode (0=off, 1=droop, 2=L droop, 4=CCC)

R

UINT16

40618

Alarm Reset Enabled

RW

UINT16

40619

Loss Of Sensing Mode

RW

UINT16

40620

No Sense To Manual Mode

RW

UINT16

40621

External Tracking Enabled

RW

UINT16

40622

Underfrequency Mode

RW

UINT16

40631

Droop Enabled

RW

UINT16

40632

L Drop Enabled

RW

UINT16

40633

CC Enabled

RW

UINT16

40634

OEL Style Mode

R

UINT16

40635

External Tracking Enabled

R

UINT16

40636

OEL Style Enabled

RW

UINT16

40637

Pre-position 2 Enabled

R

UINT16

40638

UEL Style Mode

R

UINT16

40639

OEL Option Mode

R

UINT16

40640

Pre-position Selection

R

UINT16

40641

UEL Style Enabled

RW

UINT16

40642

Voltage Matching Enabled

RW

UINT16

40643

OEL Enabled

RW

UINT16

40644

UEL Enabled

RW

UINT16

40645

SCL Enabled

RW

UINT16

40646

Internal Tracking Mode

R

UINT16

40647

External Tracking Mode

R

UINT16

40648

Voltage Matching Mode

R

UINT16

40649 to
40674

Reserved for future C4 use

R

Not

Defined

40675

Var limiter enable; 0=disable, 1=enable

RW

UINT16

40720

Enables traverse rate to pre-position 1 for the mode

RW

UINT16

40721

Enables traverse rate to pre-position 2 for the mode

RW

UINT16

40722

Enables traverse rate to pre-position 1 for the mode

RW

UINT16

40723

Enables traverse rate to pre-position 2 for the mode

RW

UINT16

40724

Enables traverse rate to pre-position 1 for the mode

RW

UINT16

40725

Enables traverse rate to the pre-position 2 for the mode

RW

UINT16

DECS-400

Modbus™ Communication

Advertising