Basler Electric DECS-400 User Manual

Page 238

Advertising
background image

226

9369700990 Rev R

Registers

Data Description

Access

Data

Format

43628

Relay 3 Contact Status

RW

UINT16

43629

Relay 3 Momentary Time

RW

UINT16

43630 to
43675

Reserved for future C11 use

R

Not

Defined

43676

Relay 4 State

RW

UINT16

43677

Relay 4 Contact Type

RW

UINT16

43678

Relay 4 Contact Status

RW

UINT16

43679

Relay 4 Momentary Time

RW

UINT16

43680 to
43725

Reserved for future C11 use

R

Not

Defined

43726

Relay 5 State

RW

UINT16

43727

Relay 5 Contact Type

RW

UINT16

43728

Relay 5 Contact Status

RW

UINT16

43729

Relay 5 Momentary Time

RW

UINT16

43730 to
43775

Reserved for future C11 use

R

Not

Defined

43776

Relay 6 State

RW

UINT16

43777

Relay 6 Contact Type

RW

UINT16

43778

Relay 6 Contact Status

RW

UINT16

43779

Relay 6 Momentary Time

RW

UINT16

43780 to
44125

Reserved for future C11 use

R

Not

Defined

Holding Registers for General ASCII and Modbus Communication Parameters

Table 46. Information Category C12—General ASCII and Modbus Communication Parameters

Registers

Data Description

Access

Data

Format

44126

Baud rate of Front communication port 0, RS-232, Data Range:1200, 2400,
4800, 9600,19200, Default 9600

R

UINT16

44127

Baud rate of Rear communication port 1, RS-485, Data Range:1200, 2400,
4800, 9600,19200, Default 9600

R

UINT16

44128

Baud rate of Rear communication port 2, RS-485, Data Range:4800,
9600,19200, Default 9600

RW

UINT16

44129

Modbus port Parity, valid only for Rear RS-485 port. ‘O’ = 79= 0x4F for Odd
Parity, ‘E’ = 69= 0x45 or Even Parity, and ‘N’ =78= 0x4E for None

RW

UINT8

44130

Modbus port Stop Bits, 1 for 1 Stop Bit, 2 for 2 Stop bits, Default value: 2

RW

UINT8

44131

DECS400 Polling Address, valid only for Rear RS-485 port. 0 for
Broadcast address, 1 to 247 for slave address, Default: 247

RW

UINT16

44132

Modbus Response Delay Time Parameter in ms (Default value: 10ms) Data
Range 0-200, step size 10

RW

UINT16

44133

System Clock Month

RW

UINT16

44134

System Clock Day

RW

UINT16

44135

System Clock Year

RW

UINT16

44136

System Clock Daylight Savings Time, 0 = Daylight Savings Time On, 1 =
Daylight Savings Time Off

RW

UINT16

44137

System Clock Hour

RW

UINT16

44138

System Clock Minute

RW

UINT16

44139

System Clock Second

RW

UINT16

44140

System Clock Time Format, 0 = 12 hour format, 1 = 24 hour format.

RW

UINT16

44141

System Clock AM/PM. 'A' = 65 = 0x41 for AM, 'P' = 80 = 0x50 for PM, 'X' =
58 = 0x3A for none

RW

UINT16

44142 to
44200

Reserved for future C12 use

R

Not

Defined

Modbus™ Communication

DECS-400

Advertising