Basler Electric DECS-400 User Manual

Page 231

Advertising
background image

9369700990 Rev R

219

Registers

Data Description

Access

Data

Format

40779

AVR mode traverse rate, adjustable from 10 to 200 seconds in 1 second
increments

RW

FLOAT

40781

VAR mode traverse rate, adjustable from 10 to 200 seconds in 1 second
increments

RW

FLOAT

40783

PF mode traverse rate, adjustable from 10 to 200 seconds in 1 second
increments

RW

FLOAT

40785

FCR mode setpoint pre-position 1; adjustment range is determined by
registers (40761-62) and (40769-70)

RW

FLOAT

40787

AVR mode setpoint pre-position 1; adjustment range is determined by
registers (40763-64) and (40771-72)

RW

FLOAT

40789

VAR mode setpoint pre-position 1; adjustment range is determined by
registers (40765-66) and (40773-74)

RW

FLOAT

40791

PF mode setpoint pre-position 1; adjustment range is determined by
registers (40767-68) and (40775-76)

RW

FLOAT

40793

FCR mode setpoint step size = setpoint range / (traverse rate x 10):[(regs.
40769-70) - (regs. 40761-62)] / [(regs. 40777-78) x 10]

R

FLOAT

40795

AVR mode setpoint step size = setpoint range / (traverse rate x 20):[(regs.
40771-72) - (regs. 40763-64)] / [(regs. 40779-80) x 20]

R

FLOAT

40797

VAR mode setpoint step size = setpoint range / (traverse rate x 20):[(regs.
40773-74) - (regs. 40765-66)] / [(regs. 40781-82) x 20]

R

FLOAT

40799

PF mode setpoint step size = setpoint range / (traverse rate x 20):[2 +
(regs. 40775-76) - (regs. 40767-68)] / [(regs. 40783-84) x 20]

R

FLOAT

40801

FCR mode setpoint's minimum (in % of rated field current), adjustable from
0 to 100%, in .1% increments

RW

FLOAT

40803

AVR mode setpoint's minimum (in % of rated generator output voltage),
adjustable from 70 to 100%, in .1% increments

RW

FLOAT

40805

VAR mode setpoint's minimum (in % of rated generator VA), adjustable
from -100 to +100%, in .1% increments

RW

FLOAT

40807

PF mode setpoint maximum, adjustable from 0.5 to 1.0, in .005 increments

RW

FLOAT

40809

FCR mode setpoint's maximum (in % of rated field current), adjustable from
100 to 120%, in .1% increments

RW

FLOAT

40811

AVR mode setpoint's maximum (in % of rated generator output voltage),
adjustable from 100 to 110%, in .1% increments

RW

FLOAT

40813

VAR mode setpoint's maximum (in % of rated generator VA), adjustable
from -100 to +100%, in .1% increments

RW

FLOAT

40815

PF mode setpoint minimum, adjustable from -1.0 to -0.5, in .005 increments

RW

FLOAT

40817

Minimum value for FCR mode setpoint's adjustable minimum (in % of rated
field current) = 0%

R

FLOAT

40819

Minimum value for AVR mode setpoint's adjustable minimum (in % of rated
generator ouput voltage) = 70%

R

FLOAT

40821

Minimum value for VAR mode setpoint's adjustable minimum (in % of rated
generator VA) = -100%

R

FLOAT

40823

Maximum value for PF mode setpoint's adjustable minimum

R

FLOAT

40825

Maximum value for FCR mode setpoint's adjustable maximum (in % of
rated field current) = 120%

R

FLOAT

40827

Maximum value for AVR mode setpoint's adjustable maximum (in % of
rated generator ouput voltage) = 110%

R

FLOAT

40829

Maximum value for VAR mode setpoint's adjustable maximum (in % of
rated generator VA) = 100%

R

FLOAT

40831

Minimum value for PF mode setpoint's adjustable maximum

R

FLOAT

40833

Step size for FCR mode setpoint's adjustable maximum (in % of rated field
current) = 0.1%

R

FLOAT

40835

Step size for AVR mode setpoint's adjustable maximum (in % of rated
generator output voltage) = 0.1%

R

FLOAT

40837

Step size for VAR mode setpoint's adjustable maximum (in % of rated
generator VA) = 0.1%

R

FLOAT

DECS-400

Modbus™ Communication

Advertising