9369700990 Rev R

215

Registers

Data Description

Access

Data

Format

40211

Relay output states b0 = watchdog, b1 = on/off, b2 = Relay 1, b3 = Relay
2, b4 = Relay 3, b5 = Relay 4, b6 = Relay 5, b7 = Relay 6, b8-b15 =
unused

R

UINT16

40212 to
40250

Not used

R

Not

Supported

40251

Phase A to B rms generator voltage

R

FLOAT

40253

Phase B to C rms generator voltage

R

FLOAT

40255

Phase C to A rms generator voltage

R

FLOAT

40257

RMS bus voltage

R

FLOAT

40259

Generator phase A current rms

R

FLOAT

40261

Generator phase B current rms

R

FLOAT

40263

Generator phase C current rms

R

FLOAT

40265

Average generator line-to-line rms voltage

R

FLOAT

40267

Average generator phase current

R

FLOAT

40269

DC field voltage

R

FLOAT

40271

DC field current

R

FLOAT

40273

Auxiliary input volts

R

FLOAT

40275

Magnitude of A-B voltage fundamental phasor

R

FLOAT

40277

Magnitude of B-C voltage fundamental phasor

R

FLOAT

40279

Magnitude of C-A voltage fundamental phasor

R

FLOAT

40281

Magnitude of line A current fundamental phasor

R

FLOAT

40283

Magnitude of line B current fundamental phasor

R

FLOAT

40285

Magnitude of line C current fundamental phasor

R

FLOAT

40287

Current input for load compensation

R

FLOAT

40289

Angle between Vab and Vca

R

FLOAT

40291

Angle between Vbc and Vca

R

FLOAT

40293

Angle between Ia and Vca

R

FLOAT

40295

Angle between Ib and Vca

R

FLOAT

40297

Angle between Ic and Vca

R

FLOAT

40299

Angle between Iaux and Vca

R

FLOAT

40301

Generator real power

R

FLOAT

40303

Generator reactive power

R

FLOAT

40305

Generator apparent power

R

FLOAT

40307

Generator power factor

R

FLOAT

40309

Generator positive sequence voltage

R

FLOAT

40311

Generator negative sequence voltage

R

FLOAT

40313

Generator positive sequence current

R

FLOAT

40315

Generator negative sequence current

R

FLOAT

40317

Generator frequency

R

FLOAT

40319

Bus frequency

R

FLOAT

40321

Null Balance or tracking error

R

FLOAT

40323

Active controller output

R

FLOAT

40325

Error signal to autotracking loop

R

FLOAT

40327

Rotor temperature

R

FLOAT

40329

Shorted diode harmonic current

R

FLOAT

40331

Open diode harmonic current

R

FLOAT

40333

VAR/PF controller output

R

FLOAT

40335

PSS terminal frequency deviation

R

FLOAT

40337

PSS compensated frequency deviation

R

FLOAT

40339

PSS washed out speed deviation

R

FLOAT

40341

PSS washed out power deviation

R

FLOAT

40343

PSS mechanical power filter output

R

FLOAT

40345

PSS signal before phase lead/lag blocks

R

FLOAT

40347

PSS signal after phase lead/lag blocks

R

FLOAT

40349

PSS signal after terminal voltage limiter

R

FLOAT

40351

Final PSS output including test signal

R

FLOAT

40353 to
40399

Reserved for future C2 use

R

Not

Supported

DECS-400

Modbus™ Communication