9369700990 Rev R

107

Cross Current Comp. Mode. This setting enables a data log report to be triggered when cross-current
compensation (reactive differential) is enabled or disabled. Selecting NO TRIGGER disables a Cross-
Current Compensation mode trigger.

Test Mode. This setting enables a data log report to be triggered when Test mode is enabled or disabled.
Selecting NO TRIGGER disables a Test mode trigger.

Level Triggers/Log Selection

The Level Triggers/Log Selection tab (Figure 75) consists of a list of parameters that can be selected to
trigger a data log report. Up to six parameters can be selected as triggers. Each parameter has a Level
Trigger Enable setting which configures a data log to be triggered when the parameter increases above
the Upper Threshold setting, decreases below the Lower Threshold setting, or either increases
above/decreases below the Upper Threshold/Lower Threshold setting. The list of parameters that can be
selected from to trigger a data log report is provided in Table 7.The Lower Threshold and Upper
Threshold setting range for each parameter is listed also.

Table 7. Data Log Report Parameter Triggers

Parameter

Unit of

Measure

Threshold

Increment

Lower

Upper

Auxiliary Voltage Input

V

–2 to 2

–2 to 2

0.01

AVR PID Error Signal Input

V

–2 to 2

–2 to 2

0.01

Bus Frequency

Hz

0 to 180

0 to 180

0.01

Bus Voltage

V

–2 to 2

–2 to 2

0.01

Comp. Frequency Deviation

Hz

–60 to 60

–60 to 60

0.01

Control Output

N/A

–32,767 to 32,767

–32,767 to 32,767

1

Cross Current Input

A

–4 to 4

–4 to 4

0.01

Field Current

A

–2 to 2

–2 to 2

0.01

Field Temperature

PU

–2 to 2

–2 to 2

0.01

Field Voltage

V

–2 to 2

–2 to 2

0.01

Frequency Response

V

–2 to 2

–2 to 2

0.01

Generator Apparent Power

PU

–2 to 2

–2 to 2

0.01

Generator Average Current

kVA

–4 to 4

–4 to 4

0.01

Generator Average Voltage

V

–2 to 2

–2 to 2

0.01

Generator Current Ia

A

–4 to 4

–4 to 4

0.01

Generator Current Ib

A

–4 to 4

–4 to 4

0.01

Generator Current Ic

A

–4 to 4

–4 to 4

0.01

Generator Frequency

Hz

0 to 180

0 to 180

0.01

Generator Power Factor

PF

–1 to 1

–1 to 1

0.01

Generator Reactive Power

kvar

–2 to 2

–2 to 2

0.01

Generator Real Power

kW

–2 to 2

–2 to 2

0.01

Generator Voltage Vab

V

–2 to 2

–2 to 2

0.01

Generator Voltage Vbc

V

–2 to 2

–2 to 2

0.01

Generator Voltage Vca

V

–2 to 2

–2 to 2

0.01

Negative Sequence Current

A

–4 to 4

–4 to 4

0.01

Negative Sequence Voltage

V

–2 to 2

–2 to 2

0.01

Null Balance

PU

–2 to 2

–2 to 2

0.01

OEL Controller Output

V

–2 to 2

–2 to 2

0.01

PF Mode Output

V

–2 to 2

–2 to 2

0.01

DECS-400

BESTCOMS™ Software