Basler Electric DECS-400 User Manual

Page 153

Advertising
background image

9369700990 Rev R

141

•

Use the AVR/FCR tab of the BESTCOMS Setting Adjustment screen to set the
generator no-load setpoint in FCR mode. The recommended setting is 20% of the rated
exciter current. ....................................................................................................................... ________

For the following steps, access the AVR Gain tab of the BESTCOMS Gain screen (Figure 101). Table 21
lists the recommended PID setting for exciter and static exciter installations.

Figure 101. BESTCOMS Gain Screen, AVR Gain Tab

Table 21. Recommended Settings for Exciter and Static Exciter Installations

PID Setting

Static Exciter

Exciter

AVR

FCR

AVR

FCR

Kp

80

—

80

—

Ki

20

—

15

—

Kd

—

—

40

—

Kg

15

1000

15

1000

Td

0.01

0.01

0.01

0.01

•

Set the Proportional Gain Kp setting. .................................................................................... ________

•

Set the Td filter setting. .......................................................................................................... ________

•

Set the FCR, Loop Gain Kg setting. ...................................................................................... ________

Recommended settings for OEL.

•

Set Ki at 3 .............................................................................................................................. ________

•

Set Kg at 1 ............................................................................................................................. ________

Recommended settings for UEL.

•

Set Ki at 10 ............................................................................................................................ ________

•

Set Kg at 1 ............................................................................................................................. ________

DECS-400

Commissioning

Advertising