9369700990 Rev R

199

Manual

Puts the DECS-400 in manual mode (latching).

Pre Position 1

Returns the active setpoint to its programmed pre position 1 level.

Raise

Raises the active setpoint (momentary).

Lower

Lowers the active setpoint (momentary).

PF Var

52J/K contact (forces the regulator in PF/var mode when it is true) (dependent upon BESTCOMS
selection).

Dual PID Selection

Activates the secondary gains (non-latching) (secondary gains are only active when the output is active).

Alarm Reset

A momentary input resets all DECS-400 alarms.

Secondary DECS

Activates the tracking mode of the DECS-400 (non-latching).

Var PF Selection

0=Droop, 1=Droop/var/PF selection available through BESTCOMS.

Droop Enabled

Acts as a permissive for the checkbox in BESTCOMS (if this output is included in the logic, or it has been
in the logic since the last time power was cycled, it must be set true before the regulator will enter droop
mode).

Line Drop

Controls line drop compensation in the same way as the Droop Enabled output.

Cross Current Compensation

Controls CCC in the same way as the Droop Enabled output.

Internal Tracking

Acts as a permissive to the BESTCOMS enable switch, but the BESTCOMS switch is not a permissive to
this output (if this output is included in the logic, or it has been in the logic since the last time power was
cycled, it must be set true before the regulator will enter this mode).

External Tracking

Controls external tracking in the same way as the Internal Tracking output.

Voltage Matching

When this is set true, voltage matching is enabled (disabled when on-line).

Below 10 Hz

Below 10 Hz alarm.

DECS-400

Programmable Logic