Setpoint Fine Adjust. Clicking the Raise button increases the active operating setpoint. Clicking the Lower
button decreases the active operating setpoint. The raise and lower increment is a function of the setpoint
range of adjustment and the active mode traverse rate. The increments are directly proportional to the
adjustment range and inversely proportional to the traverse rate.

Setpoints. Five status fields indicate the setpoints for AVR mode, FCR mode, FVR mode, Var mode, and
Power Factor mode.

System Alarms

System Alarms tab indicators are shown in Figure 68 and described in the following paragraphs.

System Alarms. When any of 27 alarm conditions (Figure 68) exist, the corresponding indicator changes
from gray to red. Clicking the RESET button resets any system alarm annunciation that is no longer
active.

Note

Two volts per hertz alarm indicators are provided on the System
Alarms tab: Excessive V/Hz and Underfrequency V/Hz. The Excessive
V/Hz indicator annunciates that V/Hz protection is active and the
Underfrequency V/Hz indicator annunciates that the V/Hz limiter is
active.

System Status. Various system operating modes (Figure 68) are listed alongside text labels that change
according to the status of each operating mode.

Figure 68. Metering Screen, System Alarms Tab

System Status

System Status tab indicators are shown in Figure 69 and described in the following paragraphs.

BESTCOMS™ Software