The DECS-400 provides automatic tracking (following) of the controlling mode setpoint by the non-
controlling setpoint. When a primary and secondary DECS-400 are used together, the secondary DECS-
400 tracks the setpoint of the primary DECS-400.

Between DECS-400 Operating Modes

Autotracking between control modes of a DECS-400 enables an operator to initiate controlled, “bumpless”
transfers between operating modes with minimal disturbance to the power system. Autotracking enables
a set of protective relays to initiate a transfer to a backup mode (such as FCR mode) when a system
failure or fault (such as a loss of sensing) is detected.

Between DECS-400 Units

A DECS-400 controller can be placed in service as a backup to a primary DECS-400 controller. The
backup DECS-400 tracks the control output of the primary DECS-400 using dedicated communication
port Com 1. In the unlikely event of a primary DECS-400 failure, excitation control is transferred to the
secondary DECS-400 with minimal system disturbance.

Data Recording and Reporting

DECS-400 data recording and reporting functions include sequence of events recording (SER), data
logging, (oscillography), and trending.

Sequence of Events

A sequence of events recorder monitors the internal and external status of the DECS-400. Events are
scanned at 50 millisecond intervals with 127 events stored per record. All changes of state that occur
during each scan are time- and date-stamped. Sequence of events reports are available through
BESTCOMS. A sequence of events record can be triggered by a change in an alarm state, a relay output,
or contact input. All of the possible, user-selected state changes are listed below.

Alarm States

Clock Reset

Excessive Volts per Hertz

Failed to Build Up

Field Overcurrent

Field Overtemperature

Field Overvoltage

Generator Overvoltage

Generator Undervoltage

Loss of Field

Loss of Field Isolation Transducer

Loss of IRIG

Loss of Sensing Voltage

Open Exciter Diode

Overexcitation Limiting (OEL)

Power Supply Low

PSS Current Unbalanced

PSS Power Below Threshold

PSS Speed Failure

PSS Voltage Limit

PSS Voltage Unbalanced

Setpoint Lower Limit

Setpoint Upper Limit

Shorted Exciter Diode

Stator Current Limiting (SCL)

System Below 10 Hz

Underexcitation Limiting (UEL)

Underfrequency (V/Hz) Limit

Relay Outputs

Relay Output 1

Relay Output 2

Relay Output 3

Relay Output 4

Relay Output 5

Relay Output 6

Start/Stop

Watchdog

Contact Inputs

AVR (Auto)

FCR (Manual)

Functional Description