LOGIC

5-57

Chapter 5

●Muting inputs: X2, X3, X6, and X7

Muting inputs are used to diagnose the status of muting devices, such as sensors or limit switches.

Intended inputs
(Terminal names)

Target safety
inputs
(Terminal
names)

Function

Muting input 1
(X2, X3)

Safety input 1
(X0, X1)

Function name

Muting input+Muting II

Muting input 2
(X6, X7)

Safety input 2
(X4, X5)

Symbol

Muting input

+

Muting

function

Safety

input

Muting

( ∞ )

Description

of

operation

This function diagnoses the status of connected
muting devices. This function diagnoses the time
interval of status transition between each input of
duplicated inputs (3s). The function does not use
a drive terminal (T2, T3, T6, T7).

Detail
information

Logic functions (5-323, 329)

Warning

Muting inputs are not safety inputs. Do not use these to construct a safety system.
The maximum time to suspend the safety function continuously (muting monitor time) is not specified
in the SafetyOne. Based on risk assessment, monitor the muting monitor time that is suitable for the
safety system, by external circuit or devices.