LOGIC

5-138


●Safety output monitor outputs: Y12 and Y13

Safety output monitor outputs are used to output the status of safety outputs in SafetyOne.

Intended outputs
(Terminal names)

Target safety outputs
(Terminal names)

Description of operation

Safety output 1 monitor output
(Y12)

Safety output 1
(Y0, Y1)

Safety output 2 monitor output
(Y13)

Safety output 2
(Y2, Y3)

When the target safety output is ON,
the monitor output is ON. When the
target safety output is OFF, this
function is OFF. The monitor output
turns OFF immediately, independent
of the preset OFF-delay time.

Note. When the safety output detects an output circuit failure, corresponding safety output monitor

output becomes a pulse outputs (1Hz). The monitor output is OFF in other errors, Initial state, or
Configuration state.


●State monitor outputs: Y14 to Y16
State monitor outputs are used to output the internal state of SafetyOne.

State

Intended outputs
(Terminal names)

Initial

Run

Configuration

Protection

Stop

State monitor output 1
(Y14)

ON

OFF

OFF

OFF

ON

State monitor output 2
(Y15)

ON

OFF

ON

ON

ON

or□

OFF

State monitor output 3
(Y16)

OFF

ON

OFF

OFF

OFF

Refer to “Chapter 4 BASIC OPERATIONS” and to “Chapter 6 TROUBLE SHOOTING” for details of
each state.

Warning

The monitor outputs are not safety outputs. Do not use these to construct a safety system.