LOGIC

5-173

Chapter 5

Intended inputs
(Terminal names)

Function

Function name

Dual channel safety input

Symbol

Dual Channel Safety

Description of operation

This function diagnoses the status of
connected safety devices. This function
diagnoses the time interval of status
transition between each input of
duplicated inputs (0.1s). The function
does not use drive terminals (T12, T13).

Safety input 6
(X12, X13)

Detail information

Logic functions (5-317)

Warning

For connected control devices, refer to “SAFETY PRECAUTIONS”.

Safety check signals (pulses signals) are sent from the drive terminals (T0, T2 to T11) to diagnose
connected safety devices and input circuits. Safety check signals can not be used as a power supply
for connected devices.

Note. Solid state outputs, such as safety light curtains, can not be connected to safety input 1 through

Safety input 5.

Note. Use safety input 1 through Safety input 5, as specified combinations, such as receive terminal

(Xn) and drive terminal (Tn). If the combinations are incorrect, SafetyOne does not work
correctly.

Note. When SafetyOne is in Run state or Protection state, input states are monitored in all safety

inputs. For example, if input monitor error is detected in safety input 2 although AUTO mode is
selected, SafetyOne detects error and transits to Protection state.

Note. If there are unused safety inputs in safety input 2 through safety input 5, connect the unused

receive terminals (Xn) to the corresponding drive terminals (Tn). If they are not connected, the
SafetyOne does not turn ON the safety outputs.

Note. If safety input 6 is not used, connect the receive terminals (X12 and X13) to a 24V DC power

supply (V+). If they are not connected, the SafetyOne does not turn ON the safety outputs.