Safety output with timer, Connects to, Description of operation – IDEC FS1A Controller User Manual

Page 383

Advertising
background image

LOGIC

5-335

Chapter 5

Safety output with timer

This function is for controlling the safety output with OFF delay timer.
As shown in Fig. 5-35, this function is comprised of a hold input (O

n

), an EDM input (I

n

), and a

safety output (Y

n

). The function output of external device monitoring input function is connected to

the EDM input (I

n

).





Fig. 5-35 Safety output with timer function circuit

Connects to

Equipment with force guided mechanisms, such as, contactors, safety relays.
Input of safety PLC, or other safety controllers.


Description of operation

The operation timing is described in Fig. 5-36 and 5-37.

I When hold input is turned ON, the safety output is turned ON after confirmation that the EDM

input is ON.

II When hold input is turned OFF, the safety output is turned OFF.
III When the OFF-delay timer is set, after the hold input is turned OFF, the safety output is

turned OFF after the set time of the OFF-delay timer. However, the monitor outputs for
safety outputs are turned OFF immediately after the hold input is turned OFF regardless of
the set time of the OFF-delay timer.

IV If the EDM input is not applied correctly (ON state of EDM input is not detected during EDM

monitoring time (1s) after hold input is turned ON, ON state of EDM input is not detected
during EDM monitoring time (1s) after safety output turns OFF, or ON state of EDM input is
not detected during EDM monitoring time (1s) after EDM input turns OFF due to the error
during safety output is OFF state), the SafetyOne changes to the Protection state, and
indicates “1” on the error LED without turning ON the safety output. (See Fig. 5-37.)

O

n

I

n

Y

V-

Ex. Contactor, safety relay

Hold

EDM

OSSD

with

OFF delay

Advertising